Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
100
6SE6400-5BB00-0BP0
P0819[3]
Copy drive data set (DDS)
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
0
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 2
Calls "Copy Drive Data Set (DDS)" function.
The list of all Drive Data Sets (DDS) are shown in the opening instructions of the Parameter List (PLI).
Index:
P0819[0] : Copy from DDS
P0819[1] : Copy to DDS
P0819[2] : Start copy
Example:
Copying of all values from DDS1 to DDS3 can be accomplished by the following procedure:
P0819[0] = 0
P0819[1] = 2
P0819[2] = 1
2. DDS 3. DDS
P0005
P0291
P0300
P0304
P0305
..
..
.
P2484
P2487
P2488
..
..
.
..
..
.
..
..
.
[0]
[1]
[2]
1. DDS
1. DDS
3. DDS
Start copy
Note:
Start value in index 2 is automatically reset to "0" after execution of function.
P0820
BI: DDS bit 0
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4095:0
Selects command source from which to read Bit 0 for selecting a drive data set (DDS).
t
0
1
2
3
(0:0)
BI: DDS bit 0
P0820
(0:0)
BI: DDS bit 1
P0821
t
0
1
2
3
CO/BO: Act CtrlWd2
r0055
r0055
CO/BO: Act CtrlWd2
r0055
r0055
.04
.04
.05
.05
r0051[1]
DDS active
Selecting DDS
approx. 50 ms
approx. 50 ms
Changeover time
Changeover time
Drive running
Drive ready
t
r0051 [2]
CO: Active DDS
.01
Level
2
Level
3