Input current ratings (continued), Class 8839 econoflex™ ac drives, Ratings – Schneider Electric ALTIVAR 58 TRX User Manual
Page 196

Class 8839 Econoflex™ AC Drives
Ratings
196
09/2003
©
2000–2003 Schneider Electric All Rights Reserved
INPUT CURRENT RATINGS (CONTINUED)
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 230 Vac
▲
Drive Controller
Catalog Number
▼
Motor Power
230 Vac 60 Hz
(HP)
5 kAIC
(0.141 mH)
(A)
22 kAIC
(0.032 mH)
(A)
Factory-mounted Line Reactor
■
Mod A09
5 kAIC (0.141 mH)
(A)
22 kAIC (0.032 mH)
(A)
58EC•3V_
1
4.9
5.6
3.3
3.5
58ED•3V_
2
8.6
9.7
5.6
5.9
58EE•3V_
3
11.8
13.4
8.1
8.5
58EF•3V_
5
19.5
22.1
14.1
14.7
58EG•3V_
7.5 26.4
30
19.9
20.6
58EH•3V_
10
35
38.2
27.5
28.6
58EJ•3V_
15
37.8
38
37.8
38
58EK•3V_
20
50.5
50.8
50.5
50.8
58EL•3V_
25
61.8
61.8
61.8
61.8
58EM•3V_
30
73.3
73.6
73.3
73.6
58EN•3V_
40
97.9
98.5
97.9
98.5
58EP•3V_
50
121.2
124
121.2
124
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 208 Vac
▲
Drive Controller
Catalog Number
▼
Motor Power
208 Vac 60 Hz
(HP)
5 kAIC
(0.141 mH)
(A)
22 kAIC
(0.032 mH)
(A)
Factory-mounted Line Reactor
■
Mod A09
5 kAIC (0.141 mH)
(A)
22 kAIC (0.032 mH)
(A)
58EC•2V_
1
5.3
6
3.7
3.8
58ED•2V_
2
9.4
10.6
6.5
6.6
58EE•2V_
3
13
14.5
9.2
9.5
58EF•2V_
5
21.4
24
16.2
17.1
58EG•2V_
7.5
29
34.7
22.9
23.3
58EH•2V_
10
38.3
44.4
31.7
32.3
58EJ•2V_
15
41.7
41.7
41.7
41.7
58EK•2V_
20
55.5
55.7
55.5
55.7
58EL•2V_
25
67
67.2
67
67.2
58EM•2V_
30
80.9
80.9
80.9
80.9
58EN•2V_
40
107.6
108.4
107.6
108.4
58EP•2V_
50
134.8
135.5
134.8
135.5
▲
Select conductor based on the input line current.
▼
The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number
continues. See page 186 for detailed description of catalog numbers.
■
Factory modification A09 is optional for 1 to 20 HP controllers and included in 25 to 100 HP controllers.