Burner Troubleshooting
SYMPTOM
CAUSE
REMEDY
Loud, high-pitched whine
Flame is too rich.
Verify pressure tap between gas valve
and blower inlet.
Turn to Page 19 and verify that the gas
regulator setting is 0.2” (0.5cm) wc
below the blower inlet pressure.
Replace gas orifice with smaller size.
Flame is “fluttery.”
Flame is too lean.
Turn to Page 19 and verify that the gas
Exhaust may have acrid
regulator setting is 0.2” (0.5cm) wc
smell or burner may fail
below the blower inlet pressure.
to stay lit.
Replace gas orifice with larger size.
Burner pulsates or
Exhaust vent is too long.
Reduce length of exhaust vent and/or
surges, especially on
number of elbows.
ignition.
Combustion appears
Flame current is not
Check for wet or damaged igniter with
normal, but flame does
being sensed.
low resistance to ground. Replace with
not stay lit.
new igniter.
Verify burner flameholder is properly
grounded.
Replace Ignition Control Module.
Heat Exchanger Troubleshooting
SYMPTOM
CAUSE
REMEDY
Boiling in heat exchanger.
Low water flow to heater.
Service pump and or filter.
May be accompanied by
Heat exchanger plugged.
Service heat exchanger. Correct water
“bumping” sounds.
chemistry.
Bypass valve stuck open.
Service bypass valve.
Thermal governor stuck
Replace thermal governor.
closed.
Sweating.
Thermal governor failed.
Replace thermal governor.