Schneider Electric DuraDrive Direct Coupled Actuators MA4X-707X User Manual
Application, Features
Printed in U.S.A.
1/10
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
Application
DuraDrive™
Direct Coupled Actuators are designed to
be used in both damper and valve control applications.
The follow general instructions are for damper
applications, refer to the Applicable Literature table for
valve literature.
The MA40-704X, MA4X-707X and MA4X-715X series
spring return actuators are used for the on-off, fail safe
control of dampers and valves in HVAC systems.
Features
•
Two-position actuator controlled by SPST controller
•
133 lb-in (15 N-m), 60 lb-in (7 N-m), and 35 lb-in
(4 N-m) torque models
•
24 Vac/DC, 120 Vac, and 230 Vac models
•
Rugged die cast housings rated for NEMA 2 / IP54
•
Overload protection throughout rotation
•
Optional built-in auxiliary switch to provide for
interfacing or signaling
•
Provides 95° of rotation
•
Visual position indicator provided
•
Provides true mechanical clockwise or
counterclockwise spring return operation for reliable
fail safe application and positive close-off in air tight
damper applications
•
Direct mount to round or square damper shafts
•
Rotation limiting available
•
MA4X-7153 series actuators can be double-
mounted (gang mounting) to accommodate high
torque application requirements
•
Five year warranty
•
MA41-707X-XXX and MA41-715X-XXX equipped
with manual override
MA40-704X Series,
MA4X-707X Series,
MA4X-715X Series
DuraDrive Series Spring Return
Two-Position Actuators
General Instructions
MA40-704X
MA40-707X
MA40-715X
MA41-707X
MA41-715X
Document Outline
- Application
- DuraDrive ™ Direct Coupled Actuators are designed to be used in both damper and valve control applications. The follow general instructions are for damper applications, refer to the Applicable Literature table for valve literature.
- The MA40-704X, MA4X-707X and MA4X-715X series spring return actuators are used for the on-off, fail safe control of dampers and valves in HVAC systems.
- Features
- . Two-position actuator controlled by SPST controller
- . 133 lb-in (15 N-m), 60 lb-in (7 N-m), and 35 lb-in (4 N-m) torque models
- . 24 Vac/DC, 120 Vac, and 230 Vac models
- . Rugged die cast housings rated for NEMA 2 / IP54
- . Overload protection throughout rotation
- . Optional built-in auxiliary switch to provide for interfacing or signaling
- . Provides 95° of rotation
- . Visual position indicator provided
- . Provides true mechanical clockwise or counterclockwise spring return operation for reliable fail safe application and positive close-off in air tight damper applications
- . Direct mount to round or square damper shafts
- . Rotation limiting available
- . MA4X-7153 series actuators can be double- mounted (gang mounting) to accommodate high torque application requirements
- . Five year warranty
- . MA41-707X-XXX and MA41-715X-XXX equipped with manual override
- Applicable Literature
- SPECIFICATIONS
- TYPICAL APPLICATIONS (wiring diagrams)
- Figure-1 Typical Wiring Diagram for 24 Vac Basic and Double Auxiliary Switch Models.
- Figure-2 Typical Wiring Diagram for 120 Vac or 230 Vac Basic and Single Auxiliary Switch Models.
- Figure-3 Typical Wiring Diagram for 24 Vac Basic and Single Auxiliary Switch Models.
- INSTALLATION
- Precautions
- Mounting
- Auxiliary Switches
- Adjusting the Switching Point
- Rotation Limitation
- Rotation Limitation for MA40-704X Series
- 1. Determine the amount of damper rotation required. The actuator stop block provides limited rotation from 40˚ to 95˚.
- 2. Loosen the screw securing the stop block to the actuator.
- 3. Slide the stop block into position, so that its edge lines up with the degree graduation on the actuator face which corresponds with the required rotation. See Figure-5.
- 4. Secure the stop block in place.
- 5. Test the damper rotation by applying power. Re-adjust if necessary.
- Figure-5 Adjusting Stop Block for Limited Rotation.
- 1. Determine the amount of damper rotation required. The actuator stop block provides limited rotation from 40˚ to 95˚.
- Rotation Limitation for MA4X-715X and MA4X-707X Series
- 1. Determine the amount of damper rotation required.
- 2. Locate the AM-689 rotation limiter on the actuator so that its edge lines up with the degree graduation on the actuator face which corresponds with the required rotation. See Figure-6.
- 3. Find the appropriate cross-hair location through the slot of the rotation limiter. This is the mounting location for the retaining screw.
- 4. Pierce through the label material to allow easy fastening of the retaining screw.
- 5. Position the rotation limiter back to the desired position, making sure the locating “teeth” on the rotation limiter are engaged into the locating holes on the actuator.
- 6. Fasten the rotation limiter to the actuator using the self-tapping screw provided.
- 7. Test the damper rotation by applying power. Re-adjust if necessary.
- Figure-6 Securing the AM-689 Rotation Limiter.
- 1. Determine the amount of damper rotation required.
- Rotation Limitation for MA40-704X Series
- CHECKOUT