Input connections, Warning – Lincoln 60 User Manual

Page 10

Advertising
background image

RECOMMENDED WIRE SIZE FOR PRO-CUT INPUT CONNECTIONS

Based on U.S. National Electrical Code Ambient Temperature 30˚C or Less

Wire Size

(Copper, 75˚C)

Rated Input

Voltage

Less than 230

230

460

Greater than 460

2 Input Wires

#8 (8.4mm

2

)

#8 (8.4mm

2

)

#10 (5.3mm

2

)

#10 (5.3mm

2

)

1 Grounding Wire

#10 (5.3mm

2

)

#10 (5.3mm

2

)

#10 (5.3mm

2

)

#10 (5.3mm

2

)

Fuse

Size

50Amp

50Amp

25Amp

25Amp

INPUT CONNECTIONS

Before starting the installation, check with the local
power company if there is any question about whether
your power supply is adequate for the voltage,
amperes, phase, and frequency specified on the
machine nameplate. Also be sure the planned instal-
lation will meet the any National Electrical Code and
local code requirements. This machine may be oper-
ated from a single phase line or from one phase of a
two or three phase line.

Models that have multiple input voltages specified on
the nameplate (e.g. 208/230/460) are shipped con-
nected for the highest voltage. If the machine is to be
operated on the lower voltage, it must be reconnected
according to the instructions on the inside of the
removable panel in the center of the rear panel.
Machine supply line entry provision is next to the
removable panel.

– 10 –

Have a qualified electrician connect the input leads to
L1 and L2 of the terminal block in accordance with
any National Electrical Code, all local codes and the
connection diagram located on the inside of the cover.
Use ferrules provided (S19117-1) for #10 wire. No
ferrule is required for #8 wire. Tighten screws to 16
in/lbs. (1.8 N.M.). See below.

ELECTRIC SHOCK can kill.
• Disconnect input power before

proceeding.

• Have a qualified electrician make

the input connections.
• Be sure the voltage, phase and frequency
of the input power is as specified on the
machine nameplate.

------------------------------------------------------------

WARNING

ELECTRIC SHOCK

can kill.

• Make certain that the input power
is electrically disconnected before
removing the screws that hold the

removable rear panel in place.

------------------------------------------------------------

WARNING

.50"

(12.7mm)

Strip Required for #10 (5.3mm

2

) Wire

Place Ferrule (S19117-1) Over Wire as Shown

Before Insertion into Machine Terminal Block.

For #10 (5.3mm

2

) AWG Wire Only

Advertising