16.0

Fault Finding

Domestic Hot Water - Follow operational sequence

Turn selector to

neon illuminated

Primary flow switch operated

Fan runs at max speed

Pump runs

Turn thermostat to max.

Open DHW tap fully. DHW

flow switch operated

Primary water is diverted

from CH system to DHW

heat exchanger and flow

microswitch operated

neon illuminated

Continuity across DHW flow

microswitch terminals and

PCB - A5 connector

terminals 5 & 6

Air pressure switch proved

neon flashing

Burner on neon

illuminated

Spark at ignition electrodes

for up to 10 seconds

Go to section ‘A’

neon flashing

Go to section ‘B’

neon flashing

Go to section ‘C’

Go to sections ‘J’ & ‘M’

neons flashing

Go to section ‘D’

Replace PCB

Turn the selector to the reset

position. If the light does not
extinguish go to section H &

K

Go to section ‘F’

neon flashing

Go to sections ‘I’ & ‘L’

DHW flow valve

senses no flow.

Primary water diverted to

CH system. DHW flow

switch released off

Close DHW tap

Burner goes out

Diverter valve spindle

assembly faulty

Pump stops

Operation sequence correct

neon flashing

Turn selector to reset

position. If regular resetting is

required or appliance still

does not operate

investigation is necessary

neon flashing

Go to section ‘E’

Burner extinguishes

after 10 seconds

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

NO

Fan stops

NO

YES

YES

YES

YES

NO

NO

DHW flow rate more than

2.5l/min.

Is mains water

filter and differential

assembly clean?

DHW flow valve diaphragm

damaged

DHW flow valve rod

obstructed

Replace DHW flow

microswitch

Replace PCB

Replace diaphragm

NO

NO

NO

YES

NO

NO

NO

NO

NO

NO

NO

NO

Reduce the DHW flow rate.

If burner does not modulate

clean DHW temperature

sensor and DHW heat

exchanger. If modulation

does not occur go to section

‘G’

Burner output modulates to

maintain temperature set at

thermostat

NO

NO