PVI Industries 27 P 125A-MXS User Manual
Low nox maxim • packaged gas water heater
LOW NOx MAXIM • PACKAGED GAS WATER HEATER
POLYSHIELD
®
POLYMER-LINED STORAGE TANK
125 GALLON TANK SERIES
MODEL NUMBER
20 P 125A-MXS
27 P 125A-MXS
40 P 125A-MXS
GPH Recovery at 40° to 120° F
245
330
490
GPH Recovery at 40° to 140° F
195
260
390
Input
Btu/h
199,000
270,000
399,000
Minimum gas inlet pressure – " W.C.
5.5
5.5
5.5
A
Cold Inlet - NPT
2
2
2
B
Hot Outlet - NPT
2
2
2
C
Drain - NPT
1
1
1
D
I - Beam Skids
3 X 34-1/2
3 x 34-1/2
3 x 34-1/2
E Overall
Depth
45
45
45
F Overall
Height
75
75
82
G
Flue Outlet Diameter
5
6
7
H
Gas Inlet - NPT
1/2
3/4
3/4
J
Motor HP 120 V, 1Ø, 60 Hz.
1/6
1/6
1/6
Motor
Amps
1.75
1.75
1.75
L
Height to Outlet
65
65
73
M
Height to Inlet
28
28
36
Approx. Shipping Weight - lbs
1020
1070
1130
Recoveries based on 82% thermal efficiency. ASHRAE 90.1 compliant.
1. Control Enclosure
2. ASME Temperature &
Pressure Relief Valve
3. 3” NPT Handhole
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see Form # PV6377.
Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 6378 02/05
(800) 784-8326
• www.pvi.com
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC PRESSURE: 9" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE
VENT CONNECTION DIAMETER EXCLUSIVELY.
FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL GAS CODE
UNDER "FAN-ASSISTED".
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.