- 26 -

Humidifier Mandatory Pre Start-up Checklist (p. 1 of 1)

Unit Serial #: _ _ _ _ _ _ _ _

# of humidifiers: _____ Tag:_____________

Unit type:

Voltage: _____V/___ph Steam output: ____lbs/hr

Customer/Job:_______________ Address: __________________________________

Inspected by: ________________ Date of inspection:____/____/____

_____________________________________________________________________________________________

WATER QUALITY:

Well water

r

City water r

Softened wate r

RO / DI water

r

Conductivity: _______mhmos

Hardness: _____ gr.

HUMIDIFIER MOUNTING:

Clearances around the unit

Acceptable

Obstruction

- Front (door opens freely?)

3ft min

____________________

- Top (steam lines)

2ft min

____________________

- Bottom (fill, drain, controls) 2ft min ____________________
- Right (main pwr)

2ft min ____________________

STEAM LINES:

CONDENSATE LINES:

- Slope up 2” per 12”

r

- Slopped back to drain

r

- Slope down ½” per 12”

r

- Trapped 2” more than static duct pressure

r

- Traps r

- Size _______

- Insulated

r

- Stainless steel

r

or plastic

r

- Length/Size _____/_______

- ________% Vertical _______% Horizontal

- 90 deg. elbows

r

qty: ____

- 45 deg. Elbows

r

qty: ____

- Can condensate be trapped anywhere in the steam line? Yes

r

no

r

WATER LINES:

- ½” at max 4ft from the unit

r

- 3/8” connection at fill

r

- water pressure: 30-80psig

r

- PVC

r

- Stainless steel

r

DRAIN LINES:

- Air gap located within 3ft of the unit

r

- Slopped to drain

r

- Size:________

CYLINDER:

- Cylinder properly installed and sitting upright

WIRING:

- No loose wires around the unit or on the PC board? yes

r

no

r

CONTROLS:

Installed Location / Wiring /Setting

Installed Location / Wiring /Setting

- High limit:

r

___________________

- Air proving:

r

___________________

- Mod controller:

r

___________________

- Other:

r

___________________

POWER:

- Voltage, amperage rating and fuse correspond to Spec Label

r

- Disconnect switch located close to humidifier

r

NH Electric Steam Humidifier