Table F: Domestic Water Heater Flow Rate Requirements

∆T = Temperature rise, °F.

∆P = Pressure drop through heat exchanger, ft.

SHL = System head loss, ft. (System head loss is based on the heater and tank placed no more than 5 feet apart and 50 feet equivalent length

of tubing and fittings.)

gpm = Gallons per minute, flow rate.

MTS = Minimum tubing size.

*Must utilize optional cupro-nickel tubes.

**With Hard Water (16-25 grains per gallon), the operating control must be set no higher than 130°F for scale free operation. For operating tem-

peratures above 130°F, a water softener must be utilized.

Model

No.

Input

MBTUH

Output

MBTUH

Soft (0–4 grains per gallon)

Medium (5–15 grains per gallon) Hard* (16–25** grains per gallon)

∆T gpm ∆P MTS SHL ∆T gpm ∆P MTS

SHL

∆T gpm

∆P

MTS

SHL

HD101

100

85

9

20

1.8 1-1/2

3.8

7

26

3.0 1-1/2

6.3

4

45

9.2

1-1/2

18.0

HD151

150

128

13

20

1.8 1-1/2

3.8

10

26

3.1 1-1/2

6.3

6

45

9.2

1-1/2

18.1

HD201

199

169

17

20

1.9 1-1/2

3.9

13

26

3.2 1-1/2

6.4

8

45

9.4

1-1/2

18.2

HD251

250

213

21

20

1.9 1-1/2

3.9

16

26

3.2 1-1/2

6.5

9

45

9.6

1-1/2

18.5

HD301

299

254

25

20

1.9 1-1/2

3.9

20

26

3.2 1-1/2

6.5

11

45

9.8

1-1/2

18.7

HD401

399

339

34

20

2.0 1-1/2

4.0

26

26

3.3 1-1/2

6.6

15

45

10.3 1-1/2

19.1

Piping—Heating Boilers

All high points should be vented. Purge valves and a

bypass valve should be installed. A boiler installed

above radiation level must be provided with a low

water cut-off device. The boiler, when used in connec-

tion with a refrigeration system, must be installed so

the chilled medium is piped in parallel with the boiler

with appropriate valves to prevent the chilled medium

from entering the boiler.

The boiler piping system of a hot water heating boiler

connected to heating coils located in air handling units

where they may be exposed to circulating refrigerated

air, must be equipped with flow control valves or other

automatic means to prevent gravity circulation of the

boiler water during the cooling cycle. It is highly recom-

mended that the piping be insulated.

Air-Separation/Expansion Tank

All boilers should be equipped with a properly sized

expansion tank and air separator fitting as shown in

the piping diagrams (Fig. 10–12).

Three-Way Valves

Valves designed to blend water temperatures or

reduce water circulation through the boiler should not

be used. Raypak boilers are high recovery low mass

boilers not subject to thermal shock. Raypak offers a

full line of electric sequencers that produce direct reset

of boiler water temperature. Refer to the Controls

Section in our Complete Catalog.

Domestic Hot Water Piping

When designing the water piping system for domestic

water applications, water hardness should be consid-

ered. Table F indicates the suggested flow rates for

soft, medium and hard water. Hardness is specified as

grains per gallon.