Common Venting

The NFGC does not address sizing guidelines for the
common venting of multiple Category IV heaters. This
is covered in the NFGC under “Engineered Vent Sys-
tems”. Table L provides boiler discharge vent
pressures at vent pressure switch and volumes of flue
products at full fire for the calculation of appropriate
vent sizing for common venting.

WARNING: Vent connectors serving any other
appliances shall not be connected into any portion of
mechanical draft systems operating under a positive
pressure. If an MVB heater is installed to replace an
existing heater, the vent system MUST be verified to
be of the correct size and of Category IV AL29-4C
vent material construction. If it is NOT, it MUST be
replaced.

NOTE: For extractor sizing, typical CO

2

levels are

8.5% for natural gas and 9.5% for propane gas and
flue temperature of 300° F.

Model

Vent

Size (in.)

Vent

Pressure

(in. WC)

Volume of

Flue Products

(CFM)

503

0.1

160

753

0.2

240

1003

6

0.3

320

1253

0.2

400

1503

0.3

480

1753

0.4

560

2003

8

0.5

640

* NOTE: Data for 100% firing rate.

Table L: Vent Pressure and Volume of Flue Products

Data

Fig. 21: Typical Common Venting

CAUTION: A listed vent cap terminal suitable for
connection to the Cat IV vent materials, adequately
sized, must be used to evacuate the flue products
from the heaters.