Installation, Flueing arrangements - vertical terminations – Regency F37-LPG User Manual

Page 9

Advertising
background image

F37 Regency

®

Rear Flued Room Sealed Freestanding Gas Heater

9

INSTALLATION

FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS

for both Residential & Manufactured Homes/Mobile Homes

Offset to Vertical Terminations

If connecting to a Dura-Vent system,
the Adapter to Dura-Vent # 640-994
is required.

Vertical Terminations

with Co-linear Flex System

The shaded area in the diagram shows the allowable vertical
terminations installed in a masonry chimney.
All vertical fl ue instal-
lations require the Flue Restrictor to be set to 32mm open. All Vertical
Flue Terminals must be Simpson Dura Vent (Abey Australia) DV 980
MAS (Australian Modifi ed.)

Vertical Terminations

using Dura-Vent Flueing System

The shaded areas in the two diagrams below show all allowable com-
binations of straight vertical and offset to vertical runs with vertical
terminations.
Maximum one 90

o

elbow. All vertical and offset to vertical

fl ue installations require Flue Restrictor to be set to 32mm open. If the fl ue
is ENCLOSED in a chase (min. size 229mm x 229mm) maintain a 32mm
clearance to combustibles. All Vertical Flue Terminals must be Simpson
Dura Vent (Abey Australia) DV 980 MAS (Australian Modifi ed.)

Straight Vertical Terminations

Flue Restrictor Position

Vent Restrictor

Vent

Restrictor

Plate

Vent Restrictor

(fully open)

Vent

Restrictor

Plate

44.5mm

44.5mm

32mm

32mm

To set the Flue restriction
as indicated in the diagram,
simply loosen the screws
and push the fl ue restrictor
plate to the correct position.
Tighten the screws.

216mm

9.1m

Max.

3.2m

Min.

1

1

1

2

4

5

6

7

8

2

1

3

9

Horizontal Distance (meters)

V

ertical

Height

(meters)