Gas fireplaces, Horizontal venting with two (2) 90° elbows, Horizontal venting with three (3) 90° elbows – Regency Zero Clearance Direct Vent Gas Fireplace P36D-NG1 User Manual

Page 7

Advertising
background image

Horizontal Venting
with Two (2) 90° Elbows

Two 45° elbows = One 90° elbow

Option

V

H+ H1

Maximum total pipe: length, of
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 8 feet.
Minimum of 1 foot between
90° elbows is required.

A)

0’ Min.

2’ Max.

B)

1’ Min.

3’ Max.

C)

2’ Min.

4’ Max.

D)

3’ Min.

5’ Max.

E)

4’ Min.

6’ Max.

F)

5’ Min.

7’ Max.

F)

6’ Min.

8’ Max.

Horizontal Venting
with Three (3) 90° Elbows

Two 45° elbows = One 90° elbow

Option

V

H

V+ V1

H + H1

Maximum total
pipe: length, of
all sections, must
not exceed 30
feet.
Total horizontal
sections must not
exceed 8 feet.
Minimum of 1
f o o t b e t w e e n
90° elbows is
required.

A)

0’ Min.

1’ Max.

1’ Min.

2’ Max.

B)

1’ Min.

2’ Max.

3’ Min.

3’ Max.

C)

2’ Min.

2’ Max.

5’ Min.

4’ Max.

D)

3’ Min.

2’ Max.

7’ Min.

5’ Max.

E)

4’ Min.

3’ Max.

9’ Min.

6’ Max.

F)

5’ Min.

4’ Max.

10’ Min.

7’ Max.

G)

6’ Min.

5’ Max.

11’ Min.

8’ Max.

H)

7’ Min.

6’ Max.

12’ Min.

9’ Max.

P36 - P36D Gas Fireplace

41

June 2007 Regency Product Specifi cations Book

Gas Fireplaces

Gas Fir

eplaces