Electrical requirements installation – Trane SCWH User Manual

Page 20

Advertising
background image

20

PKG-SVX14A-EN

electrical
requirements

Installation

RLA

LRA

qty.

hp

FLA

qty.

hp

FLA

qty

SC*H0303....

208-230V/60Hz/3Ph

12.9

77.0

0.5

2.21

1

18.3

30

3.15

19.3

30

SC*H0304....

460V/60Hz/3Ph

5.7

35.0

1.00

8.1

15

1.42

8.5

15

SC*H0305....

575V/60Hz/3Ph

4.8

31.0

0.80

6.8

15

1.14

7.1

15

SC*H0503....

208-230V/60Hz/3Ph

22.9

155.0

5.00

33.6

50

5.81

34.4

50

SC*H0504....

460V/60Hz/3Ph

10.7

75.0

2.50

15.9

25

2.63

16.0

25

SC*H0505....

575V/60Hz/3Ph

8.5

54.0

1.50

12.1

20

2.10

12.7

20

SC*H0753....

208-230V/60Hz/3Ph

27.9

164.0

6.30

41.2

60

5.81

40.7

60

SC*H0754....

460V/60Hz/3Ph

13.6

100.0

3.10

20.1

30

2.63

19.6

30

SC*H0755....

575V/60Hz/3Ph

10.2

78.0

2.40

15.2

25

2.10

14.9

25

SC*H1003....

208-230V/60Hz/3Ph

22.9

155.0

6.30

57.8

80

13.70

65.2

80

SC*H1004....

460V/60Hz/3Ph

10.7

75.0

3.10

27.2

35

6.18

30.3

40

SC*H1005....

575V/60Hz/3Ph

8.5

54.0

2.40

21.5

30

4.94

24.1

30

SC*H1203....

208-230V/60Hz/3Ph

25.4

147.7

9.40

66.5

90

13.70

70.8

90

SC*H1204....

460V/60Hz/3Ph

11.8

75.0

4.60

31.2

40

6.18

32.7

45

SC*H1205....

575V/60Hz/3Ph

9.3

59.6

3.40

24.4

30

4.94

25.9

35

SC*H1503....

208-230V/60Hz/3Ph

27.9

164.0

9.40

72.2

100

13.70

76.5

100

SC*H1504....

460V/60Hz/3Ph

13.6

100.0

4.60

35.2

45

6.18

36.8

50

SC*H1505....

575V/60Hz/3Ph

10.9

78.0

3.40

27.9

35

4.94

29.5

35

12

2

tons

MFS / MCB

model

voltage

compressor

evap. fan motor

min. circuit

ampacity

10

2

2

1

2

1

evaporator standard motor

evaporator oversized motor

evap. fan motor

MFS /

MCB

min. circuit

ampacity

5

1

2

1

5

1

3

1

1

1

5

1

1

1

7.5

1

2

1

3

1

5

1

15

2

3

1

Table I-ER-1. Model SCWH/SCRH

electrical data

WARNING

Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure power
cannot be inadvertently energized.
Failure to disconnect power before
servicing could result in death or
serious injury.

CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to
accept other type conductors. Failure
to use copper conductors may result
in equipment damage.

Notes:
1. Voltage range:
Nominal voltage 208 - 230V - acceptable range: 187 - 253V
Nominal voltage 460V - acceptable range: 414 - 506V
Nominal voltage 575V - acceptable range: 518 - 633V
2. Ampacity is calculated per UL formula, ampacity = (1.25 x compressor RLA + sum of the second compressor RLA (if

used) + evaporator motor FLA

3. Maximum fuse size is calculated per UL formula, MFS = (2.25 x compressor RLA) + sum of second compressor RLA (if

used) + evaporator motor FLA