Tracer AdaptiView

TM

Controller

Today's centrifugal chillers offer predictive controls that anticipate and compensate for load

changes. Other control strategies made possible with the Tracer AdaptiView

TM

controls are:

Feedforward Adaptive Control

Feedforward is an open-loop, predictive control strategy designed to anticipate and compensate

for load changes. It uses evaporator entering-water temperature as an indication of load change.

This allows the controller to respond faster and maintain stable leaving-water temperatures.

Soft Loading

The chiller controller uses soft loading except during manual operation. Large adjustments

due to load or setpoint changes are made gradually, preventing the compressor from cycling

unnecessarily. It does this by internally fi ltering the setpoints to avoid reaching the differential-to-

stop or the current limit. Soft loading applies to the leaving chilled-water temperature and current-

limit setpoints.

Multi-Objective Limit Arbitration

There are many objectives that the controller must meet, but it cannot satisfy more than one

objective at a time. Typically, the controller’s primary objective is to maintain the evaporator leaving-

water temperature.

Whenever the controller senses that it can no longer meet its primary objective without triggering

a protective shutdown, it focuses on the most critical secondary objective. When the secondary

objective is no longer critical, the controller reverts to its primary objective.

Fast Restart

The controller allows the CenTravac chiller to restart during the postlube process. If the chiller shuts

down on a nonlatching diagnostic, the diagnostic has 30–60 seconds to clear itself and initiate a

fast restart. This includes momentary power losses.

Building Automation and Chiller Plant Control

Trane Tracer Summit

TM

building automation systems

include pre-engineered and fl exible control for

chiller plants. It can control the operation of the

complete installation: chillers, pumps, cooling

towers, isolating valves, air handlers and terminal

units.Trane can undertake full responsibility for an

optimized automation and energy management

for the entire chiller plant.

The main functions are:

• Chiller sequencing: equalizes the number of

running hours of the chillers. Different control

strategies are available depending on the

confi guration of the installation.

• Control of the auxiliaries: includes input/output

modules to control the operation of the various

auxiliary equipments (water pumps, valves,

cooling towers, etc.)