Quick start, Hardware installation – Western Telematic IPS-800-D20 User Manual

Page 11

Advertising
background image

3-1

3. Quick Start

This Quick Start Guide describes a simplified installation procedure for the

IPS-800-D20, IPS-800E-D20, IPS-1600-D20 or IPS-1600E-D20 hardware,

which will allow you to communicate with the unit in order to demonstrate

basic features and check for proper operation.
Note that this Quick Start Guide does not provide a detailed description of unit

configuration or discuss advanced operating features. For more information,

please refer to the Installation, Configuration and Operation sections in this

User's Guide.

3.1. Hardware Installation

3.1.1.

Apply Power to the IPS

Refer to power rating nameplate on the IPS back panel, and then connect the

unit to an appropriate power source. Note that the IPS features two separate

AC inputs and two separate power busses; connect the power cables (supplied

with the unit) to the unit's Circuit "A" and Circuit "B" Power Inlets, install

the cable keepers, then connect the cables to an appropriate power source.

Refer to the table below for information concerning power requirements and

maximum loads.

Model
Number

Total

Outlets

Input

Voltage

Max. Load

per Outlet

Max. Load

per Bus

Max. Load

per Unit

IPS-800-D20

8

100 to

120 VAC

15 Amps

20 Amps

40 Amps

IPS-800E-D20

8

100 to

240 VAC

15 Amps

20 Amps

40 Amps

IPS-1600-D20

16

100 to

120 VAC

15 Amps

20 Amps

40 Amps

IPS-1600E-D20

16

100 to

240 VAC

15 Amps

20 Amps

40 Amps

Set the Main Power Switch in the ON position; the ON LED should light, and

the RDY LED should begin to flash.