Weil-McLain 88 Water and Steam Boilers — Series 2 —

For Gas, Light Oil, & Gas/Light Oil-Fired Burners

2

Part No. 550-142-025/0508

Burner specifications and settings

Burner data — Natural gas — Modulating

Table 1

Boiler

Model

Number

Burner

Model

Number

Pressure

Drop Thru

Gas Train .

Manifold

Pressure

Gas Pressure Required at

Gas Control Inlet

Gas Pilot

Pressure

Combustion

Head

Setting

Combustion

Air Settings

Servo Motor Cam

Position Settings

Min

Max

Inches W.C. Inches W.C.

Inches W.C

Inches W.C

Inches W.C.

488R

RS28/M

0.75

3.30

4.05

14

5.00

3

27

52

0

22

90

488

RS28/M

0.75

3.60

4.30

14

5.00

4

27

52

0

22

90

588

RS38/M

1.30

3.70

5.00

14

5.00

2

17

70

0

25

90

688

RS50/M

1.83

2.90

4.73

14

2.70

3

16

65

0

18

90

788

RS50/M

2.40

3.50

5.85

14

2.50

4

28

85

0

20

90

888

RS70/M

2.98

3.70

6.63

14

8.25

3

2.5

7.0

130

0

35

988R

RS70/M

3.16

3.87

7.03

14

8.25

4

2.5

7.5

130

0

35

988

RS70/M

3.16

4.10

7.28

14

8.25

5

2.5

7.5

130

0

35

1088R

RS70/M

3.00

4.65

7.65

14

6.50

8

3.0

8.5

130

0

40

1088

RS70/M

3.00

4.90

7.90

14

6.50

9

3.0

8.5

130

0

40

1188

RS100/M

3.80

3.10

6.90

14

6.50

4

2.5

6.0

130

0

35

1288

RS100/M

3.82

3.63

7.45

14

7.50

4

3.0

6.5

130

0

35

1388

RS100/M

2.41

4.50

6.91

14

7.60

3

2.5

9.0

130

0

30

1488

RS130/M

3.76

3.30

7.01

14

7.80

5

2.0

7.0

130

0

50

1588

RS130/M

4.09

3.50

7.59

14

7.20

7

2.5

7.0

130

0

50

1688R

RS130/M

3.19

3.45

6.64

14

7.20

8

2.5

8.5

130

0

30

1688

RS130/M

3.19

3.70

6.89

14

7.20

9

2.5

8.5

130

0

30

1788

RS130/M

3.70

4.80

8.50

14

7.20

9

2.5

9.0

130

0

55

1888

RS190/M

3.71

3.50

7.21

14

5.00

0

0.5

3.8

130

0

45

Burner capacities listed for elevations up to 2,000 feet. For higher eleva-

1.

tions, consult local Weil-McLain distributor/agent or sales office.
Gas ratings based on natural gas with heating value of 1,000 Btu per

2.

cubic foot and specific gravity of 0.60. Gas burners for other gases are

available. Consult local Weil-McLain distributor/agent or sales office.
Boiler-burner unit to be adjusted to achieve +0.10 inches W.C. pressure

3.

at the flue collar, resulting in positive pressure in firebox as listed.
Minimum gas pressures listed are subject to variations due to job condi-

4.

tions. Gas burners for other gas pressures are available. Consult local

Weil-McLain distributor/agent or sales office.
All settings and pressures shown are for initial start-up. Final values

5.

should be confirmed with combustion analysis.
Gas train sizes for models 488R to 1288 are based on a supply pressure

6.

to the regulator of 7 inches W.C. Gas train sizes for models 1388 to

1888 are based on a supply pressure to the regulator of 12 inches W.C.

Optional trains are available for other pressures upon request.
Gas Control Systems:

7.

OO: On - Off operation. Single-position air damper

LHL: Low-high-low-off firing conditions – two-position air and fuel

controlled by separate motor, open damper pre-purge.
MOD: On - Off operation with proven low fire start and full modulating

firing conditions. Proportional motor drives fuel metering valve and
combustion air damper according to firing conditions; open damper
pre-purge.

120/60/1 control circuit is used for all burners. Control circuit trans-

8.

former is available as an option.
Airflow safety switch is standard for all gas and combination gas/light

9.

oil units.

Burners will be completely assembled and wired (except gas train) and

10.

factory test-fired. Burners listed by Underwriters Laboratories, Inc.,

state of Connecticut, Fire Marshal state of Massachusetts, city of New

York MEA, and others.
Special controls can be provided to meet other code requirements not

11.

listed. Consult your local Weil-McLain distributor/agent or sales office.

Electric gas pilot will be furnished as standard equipment on all gas and

combination gas/light oil units.
Direct spark ignition is standard for light oil units. Direct spark ignition

12.

is available as an option for combination gas/light oil units. Consult

your local Weil-McLain distributor/agent or sales office.
All 3 phase models require a separate 120/60/1 control voltage supply.

13.

Combustion Controls:

14.

Siemens LFL 1.335 flame safeguard control monitors the oil or gas

burner flame with visual diagnostic window, provides pre-purge and

post purge, provides switching necessary to allow firing rate motor to

be driven to both low fire and high fire positions, prevent start up if

pre-ignition interlocks are open and has low fire start proven circuit.

In the event pre-ignition interlock circuit or running interlock circuit

does not “prove”, system will lock out on safety. Ultra violet sensitive

electronic flame detector is standard.

All units require a single SPDT controller for LHL firing rate opera-

15.

tion.
Modulating units 488R to 788 require a 120v bumping type signal or

16.

PID control for modulation.
Modulating units 888 to 1888 require a 4 – 20mA, 0 – 10vdc or 135 ohm

17.

signal for modulation.
Motor relay or contractor will be furnished on all units.

18.

Notes for Table 1, Table 2 and Table 3