York CHAMPION PLUS DNP024 User Manual

Page 30

Advertising
background image

036-21366-003-C-0405

30

Unitary Products Group

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125º F out-
door temperature, exceeding maximum load criteria ARI
Standard 210/240. The compressor, with standard controls,
shall be capable of operation down to 45º F outdoor tempera-
ture. Accessory low ambient kit shall be available for opera-
tion to 0º F.

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.

Advertising
This manual is related to the following products: