Zf/zr/xp036-060 disconnect, Zf/zr/xp036-060 utilities entry, Zf/zr/xp036-060 minimum clearances – York R-410A User Manual

Page 100: Zf/zr/xp036-060 roof curb dimensions

Advertising
background image

251933-YTG-J-1009

100

Johnson Controls Unitary Products

ZF/ZR/XP036-060 Disconnect

ZF/ZR/XP036-060 Roof Curb Dimensions

Disconne

ct Switch Location

and Motor Access Panel for
Unit with “Belt-Drive” Option

Control Box Access

A,B
Wiring Entry
(See Detail “B”)

Mounting Bracket for
Disconnect Switch
(Field Supplied)

Field-Supplied Disconnect
Switch Location

Blower Motor Access

Filter Access

Dot Plugs

ZF/ZR/XP036-060 Utilities Entry

Hole

Opening Size (Dia.)

Used For

A

7/8” KO

1

1. Opening in the bottom to the unit can be located by the

slice in the insulation.

Control Wiring

2

2. Do not remove the 2” knockout ring.

Side

Bottom

B

2” KO

1

Power Wiring

Side

Bottom

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

ZF/ZR/XP036-060 Minimum Clearances

Location

Clearance

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

Air/Motorized Damper)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

Right Side (Cond. Coil)

24”

Below Unit

1

1. Units may be installed on combustible floors made from

wood or class A, B, or C roof covering material.

0”

Above Unit

2

2. Units must be installed outdoors. Overhanging structures

or shrubs should not obstruct condenser air discharge
outlet.

72” (For

Condenser Air Discharge)