Door open holding torque, Response time of door open holding torque, Door open high speed 2 – Delta 1.07 VFD-D D User Manual

Page 72: Door open acceleration time 2, Door open deceleration time 2, Door open holding torque 2, Door open time-out setting, Holding time for od (open door)terminal

Advertising
background image

Chapter 4 Parameter Settings|DD Series


4-48

Door Close
Holding Speed

Open Door (R EV)

Door Open Limi t

0.0%

100.0%

Close Door (FWD)

04.00

Door Open

Speed

by Ini tial

04.08

Door Open
Acceleration

Time 1

04.09

Door Open
Deceleration

Time 1

04.03

Door Open H igh Speed 1

04.05

Door Open
Final Speed

04.01

Door Open D istance
by Ini tial Speed

04.04

Door Open

Final Speed

by

Begi ns

04.06

Door Open
by Holding

Speed Begins

04.07

Door Open
Holding Speed

05.03

Door Close

High Speed 1

D oor Close

Accel er ation Time 1

05.05

05.04

05.06

by

Door Close

Holding

Speed

Begins

05.07

05.09

05.01

Door Close

Distance by
Ini tial Speed

05.00

Door Close

Ini tial Speed

Door Close Limit

Door Close
Final Speed

Door Close
Final Speed

Door Close
by Final Speed

Begi ns

05.08

Door Open Holding Torque

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 20.0

Settings 0.0~100.0% (AC drive’s rated current)

Response Time of Door Open Holding Torque

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.20

Settings 0.01~10.00sec

When the door is in the open complete position, it needs holding torque to keep the door still in complete

position. To prevent motor overload, holding torque should be set within a limit.

Door Open High Speed 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 30.00

Settings 0.00~400.0Hz

Door Open Acceleration Time 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 1.0

Settings 0.1~3600sec

Door Open Deceleration Time 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 1.0

Settings 0.1~3600sec

Door Open Holding Torque 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.0

Settings 0.0~150.0% (AC drive’s rated current)

Door Open Time-out Setting

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.0

Settings 0.0~180.0sec (0.0 sec: Disable)

Holding Time for OD (Open Door)Terminal

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.0

Settings 0.0~999.9sec (999.9 sec for always holding)

This parameter is used to clear the OD terminal signal (door open signal) when door open complete.

During the holding period, AC Motor Drive will still be in RUN status. After holding time, AC Motor Drive

will STOP. The holding time is valid only when door open has reached the complete position.

Advertising