Object

Name

Description

R/W

NV

Units

Range

Additional Information

AI19

KW_Present_

Demand

Total Real Power

Present Demand

R

kW

0 - Max_Power (AI76)

AI20

KVAR_

Present_

Demand

Total Reactive Power

Present Demand

R

kVAR

0 - Max_Power (AI76)

AI21

KVA_Present_

Demand

Total Apparent Power

Present Demand

R

kVA

0 - Max_Power (AI76)

AI22

KW_Max_

Demand_

Import

Total Real Power Max

Demand Import

R

NV

kW

0 - Max_Power (AI76)

AI23

KVAR_Max_

Demand_

Import

Total Reactive Power

Max Demand Import

R

NV

kVAR

0 - Max_Power (AI76)

AI24

KVA_Max_

Demand_

Import

Total Apparent Power

Max Demand Import

R

NV

kVA

0 - Max_Power (AI76)

AI25

KW_Max_

Demand_

Export

Total Real Power Max

Demand Export

R

NV

kW

0 - Max_Power (AI76)

AI26

KVAR_Max_

Demand_

Export

Total Reactive Power

Max Demand Export

R

NV

kVAR

0 - Max_Power (AI76)

AI27

KVA_Max_

Demand_

Export

Total Apparent Power

Max Demand Export

R

NV

kVA

0 - Max_Power (AI76)

AI28

Reserved_

AI28

(Reserved_AI28)

R

Returns QNAN or any value

AI29

E51H2: Pulse

Count

E51H5: Pulse_

Count_1

E51H2: Pulse Count
E51H5: Pulse Count 1

R

0 - 4294967040

Running count of contact closures on Pulse Input 1 since last reset. Write 16498

(0x4072) to Present_Value of AV1 to reset both pulse counters to 0 (not used

on the E51H5).

AI30

E51H2:

Reserved

E51H5: Pulse_

Count_2

E51H2: Reserved
E51H5: Pulse Count 2

R

0 - 4294967040

E51H2: Reserved
E51H5: Pulse Count 2; Running count of contact closures on Pulse2 input since

last reset. Write 16498 (0x4072) to the Present_Value property of Analog_

Value object AV1 to reset both Pulse Counters to 0.

AI31

KWh_

Import_A

Real Energy Import

Phase A

R

NV

kWh

0 - 3.4+E38

AI32

KWh_

Import_B

Real Energy Import

Phase B

R

NV

kWh

0 - 3.4+E38

AI33

KWh_

Import_C

Real Energy Import

Phase C

R

NV

kWh

0 - 3.4+E38

AI34

KWh_

Export_A

Real Energy Export

Phase A

R

NV

kWh

0 - 3.4+E38

AI35

KWh_

Export_B

Real Energy Export

Phase B

R

NV

kWh

0 - 3.4+E38

AI36

KWh_

Export_C

Real Energy Export

Phase C

R

NV

kWh

0 - 3.4+E38

AI37

KVARh_Q1_A Reactive Energy Q1

Phase A

R

NV

kVARh 0 - 3.4+E38

The Units property of object AI37 reports that these units are kWh because there

is no unit type in the BACnet standard for kVARh

AI38

KVARh_Q1_B Reactive Energy Q1

Phase b

R

NV

kVARh 0 - 3.4+E38

The Units property of object AI38 reports that these units are kWh because there

is no unit type in the BACnet standard for kVARh

Analog_Input Objects (cont.)