Installation Guide

Power Monitoring

E51H2A, E51H5A

TM

Use this section to enter:

- BACnet communication parameters

- CT (Current Transducer) output voltage and input current ranges

- The service type to be monitored

These instructions assume the meter is set to factory defaults. If it has been previously configured, check all optional values.

A. To Navigate to the Setup screens:

1. Press

+

+

or

repeatedly until SETUP screen appears.

2. Press to get to the PASWD screen.

3. Press to move through the digits. Use the

+

+

or

buttons to enter your password (the default is 00000).

4. Press to move to the first Setup screen (S BAC)

5. Use

+

+

or

to select the parameter screen you want to set.

6. After you set the parameters you want, use

+

+

or

to select the next Setup screen or to exit the Setup screens (return to

SETUP

).

B. To Enter BACnet communication parameters

1. Navigate to the S BAC (set BACnet) Setup screen (see section A above).

2. Press to go to the MAC screen and through the address digits. Use

+

+

or

to select the BACnet MAC address (default is

001

).

3. Press to accept the value and go to the KBAUD screen. Use

+

+

or

to select the baud rate (default is 76.8K).

4. Press to go to the ID1 screen and through the upper four digits of the Device Instance. Use

+

+

or

to select the ID digits.

The setup screen splits the Device ID into two parts, the most significant four digits (ID1) and the least significant three digits
(ID2). The E51HxA supports BACnet Device ID values from 1 to 4,193,999. Units are shipped with a factory default setting that is
pseudo-randomly generated in the range from 1,000,000 to 3,097,151.

5. Press to accept the value and go to the ID2 screen and through the lower three digits of the Device Instance. Use

+

+

or

to

select the ID digits.

6. Press to accept the value and go back to the S BAC screen.

C. To Enter the CT (current transducer) output voltage and input current ranges:

1. Navigate to the S CT (Set Current Transducer) Setup screen (see section A above).

2. Press to go to the CT SZ screen and through the digits. Use

+

+

or

to select the CT size in amps (default is 100).

3. Press to accept the value and go back to the S CT screen.

D. To Enter the service type to be monitored:

1. Navigate to the S SYS (Set System) Setup screen (see section A above).

2. Press to go to the SYSTM screen. Use

+

+

or

to select the configuration (see wiring diagrams - default is 3LN-1N).

3. Press to go back to the S SYS screen.

For full setup instructions, see the configuration instructions on the following pages.