Franklin Fueling Systems TS 550 evo Fuel Management System Installation User Manual

Page 23

Advertising
background image

23

4-20mA Analog Input Module (420IB)

The Analog Input Module has 8 identical channels for loop powered 

IS sensors with a 4-20 mA interface. The TS-550 evo series can 

support up to 24 inputs (3 modules with 8 inputs each) depending 

on available space in your console. The Analog Input Module 

will most likely be used with: line leak pressure transducers, tank 

pressure sensors and vacuum sensors.

4-20mA Input

Module

RUN

ERR

+

+

+

+

+

+

+

+

Vacuum

Sensor

+ (BLK)

- (White)

Tank Pressure Sensor

- (BLK)

+ (RED)

- (BLK)

+ (RED)

LSU500

Hazardous Location

Class I, Division 1, Group

D, Group IIA, Zone 0

Non-Hazardous

Location

Figure 21: 420IB Connections

Note: All components located in the hazardous area must be Third Party Certified and have appropriate Entity 

Parameters (see Control Drawing 000-1722 in the back of this manual for further information).

Analog Input Module Specifications

Number of Channels: 8
Safety Rating:

Class I, Division 1, Group D, [Ex ia] IIA

Entity Parameters

  Uo = 26.25 V

  Io = 98.2 mA

  Co = 1.25 uF

  Lo = 14.7 mH

  Po = 0.64 W