Doc. #: 026-069-B0 Rev F
8.3.4 AC Mains Lost
The
AC Mains Lost
alarm happens when the AC input does not meet the correct voltage, phase, or frequen-
cy. When AC mains is lost the UPS goes into Inverter Mode. This alarm is sometimes accompanied by other
alarms.
Both the T2S and CXC software give inverter alarm
AC Mains Source Lost
when a column is not used (or ac-
cidentally added) in the AC Input Group in the
Inverters>Group Mapping
screen.
8.3.5 Manual Off
The Manual Off alarm happens when one or more inverters have been turned off in the group mapping
screen.
8.3.6 Phase Not Ready
Phase not ready alarm happens when the inverter thinks it should be in a certain phase and the input to it is
another phase. This can be correct either by changing the input wiring to the AMPS80 HP or by changing the
phase in the group mapping settings screen.