6.9.7 Setting the Date and Time
Table N — Setting the Date and Time
Enter command
UPS display
Description
clock
and press Enter
*clock=12/31/07 22:00:00
Returns the current date and
time.
clock=010107 120000
and
press Enter
*clock=01/01/07 12:00:00
†
Sets the date and time to Jan
01, 2007, 12:00 pm.
Notes:
1. Time is displayed in the 24 hours clock format.
2. Changing the mm/dd/yy format with DATE SEL on the LCD Control menu does not change
the RS-232 mm/dd/yy format.
3. If the Alpha Micro has been in storage or switched off for a prolonged period, the backup
Lithium coin battery could be drained and may not correctly keep a backup of the date and
time you entered. After switching on the Alpha Micro check the date and time settings. The
Alpha Micro should display the current date and time. If it displays the date as "00:01:00",
then the battery is spent and you need to ask a qualified service personnel to replace the
lithium coin battery. See "Troubleshooting".
* Indicates that the Alpha Micro has responded to the command you entered.
† If the date or time change is invalid, the Alpha Micro will return the time and date it was set to
before you tried making the change. The date and time must be entered as one complete line
command. You cannot change only the time or the date alone. Both must be set at the same
time. If you make a mistake, press