Wiring diagram – Bray 52 Series User Manual

Page 12

Advertising
background image

BRAY Series 52 Valve Status Monitor

Operation and Maintenance Manual

10

DC Version 10-30VDC NPN (Sinking)

+

-

PIN 1

PIN 2

PIN 4

PIN 3

LOAD 2

LOAD 1

PNP

PNP

S2

S1

10 to 30 Vdc

WIRING DIAGRAM

Specifications:

Operating Voltage

10 to 30VDC

Target Type

Metallic

Electrical Configuration

DC - NPN

Maximum Switching Current

200mA

Output Voltage Drop

< 2VDC

Residual Current (Off State Current)

20μA

DC Intrinsically Safe Version

WARNING

I.S. S52 must be used in conjunction with I.S. barrier. Installation and wiring should
be carried out by trained personnel who will ensure that the work complies with local
standards & NEC practices

M12 X1

CONNECTOR

PINOUT

DIAGRAM

KEY

4

3

1

2

!

PIN 1

PIN 4

PIN 2

PIN 3

+

+

_

_

Any approved Intrisically Safe
apparatus with Entity Concept param-
eters as follows:
Voc or Vt

≤ 15V

Isc or It

≤ 53mA

Ca = Ccable + 220nF
La > Lcable + 280 uH

Any approved Intrisically Safe
apparatus with Entity Concept param-
eters as follows:
Voc or Vt

≤ 15V

Isc or It

≤ 53mA

Ca = Ccable + 220nF
La > Lcable + 280 uH

S1

S2

Specifications:

Operating Voltage

7 to 12VDC

Target Type

Metallic

Electrical Configuration

NAMUR

WIRING DIAGRAM