Delta Controls DPR-2000 User Manual

Page 30

Advertising
background image

A

28 IOM-DPCDPR-A: FEB 2014

Descriptions

EXIT

return from the local Menu to the normal operation of the transmitter

UNIT

menu process variable units. Options:

IN_H2O inches of water at a temperature of 68 ° Fahrenheit
IN_HG

inches of mercury at a temperature of 68 ° Fahrenheit

FT_H2O foot of water a temperature of 68 ° Fahrenheit
MM_H2O mm of water at a temperature of 68 ° Fahrenheit
MM_HG mm of mercury at 0 ° C
PSI
BAR

bar

MBAR

millibar

G/SQCM grams per square centimetres
KG/SQCM kilogram per square centimetres, technical atmosphere
PA

pascal

KPA

kilopascal

TORR

tor (mm Hg)

ATM

physical atmosphere

M_H2O meter of water at 4 ° C
MPA

megapascal

INH2O@4 inch of water at a temperature of 4 ° C
MMH2O@4 mm of water at 4 ° C

DAMPIN

menu damping of process variable [s]. You can choose 0,2,5,10,30,60 [s]

TRANSF

type of current output characteristic Menu. Options:

LINEAR linear
SQRT

square root

SPECIA us

er’s special

SQUARE square

%SQRT

menu of, point insensitivity of square root characteristics. To select 0%, 0.2%, 0.4%, 0.6%,
0.8%, 1.0% range

PVZERO

pressure zeroing

.

SETURV

setting the upper range value by the done pressure

SETLRV

setting the lower range of values set by the done pressure

RESET

reboot your transmitter

LCD1VR

assigning a process variable to LCD1. Options:

CURREN current in the line in [mA]
PERCEN percent of the set range - controling in%

LCD2VR

assigning a process variable to LCD2. Options:

PRESS pressure value in units UNIT
USER

pressure value in user’s units

Scaling of the user range and record of the user units can be made using a computer or
communicator, see → HART command No. 244.245

SENS_T

sensor temperature value in the pressure header in °

CPU_T

CPU electronics board temperature value - in º C

LCD2DP

setting the decimal point position on LCD2. Options:

XXXXX·
XXXX·X
XXX·XX
XX·XXX
X·XXXX

In a situation where the value provided to display on the display LCD2 can not be
displayed properly due to the position of the decimal point, this is indicated by displaying
the four flashing dots • • • •. In this case, you must enter to the local menu setting and
move the decimal point respectively to the right.

FACTOR

back to factory settings (removing of current and pressure calibrations).

MID_WP

blocking records / change the parameters associated with transmitter metrology

ON

switch on blocking

OFF

switch of blocking