AAON RL-240 User Manual
Page 69
69
Table 28 - RL-045 to RL-125 and RL-135 High Efficiency Bag Filters
Standard Position (Upstream of the Cooling Coils)
Feature
Quantity / Size
Type
6A
6B
Pre Filter
High Efficiency Filter
J
N
12 / 24” x 24”
4 / 24” x 20”
2” Pleated,
30% Eff, MERV 8
30” Bag,
85% Eff, MERV 13
K
12 / 24” x 24”
4 / 24” x 20”
2” Pleated,
30% Eff, MERV 8
30” Bag,
95% Eff, MERV 14
J
P
16 / 24” x 24”
2” Pleated,
30% Eff, MERV 8
30” Bag,
85% Eff, MERV 13
K
16 / 24” x 24”
2” Pleated,
30% Eff, MERV 8
30” Bag,
95% Eff, MERV 14
L
N
12 / 24” x 24”
4 / 24” x 20”
4” Pleated,
30% Eff, MERV 8
30” Bag,
85% Eff, MERV 13
M
12 / 24” x 24”
4 / 24” x 20”
4” Pleated,
30% Eff, MERV 8
30” Bag,
95% Eff, MERV 14
L
P
16 / 24” x 24”
4” Pleated,
30% Eff, MERV 8
30” Bag,
85% Eff, MERV 13
M
16 / 24” x 24”
4” Pleated,
30% Eff, MERV 8
30” Bag,
95% Eff, MERV 14
Table 29 - RL-045 to RL-125 and RL-135 High Efficiency Bag Filters
Pre Position (Upstream of the Blow-Through Fans)
Feature
Quantity / Size
Type
6A
6B
Pre Filter
High Efficiency Filter
Y
N
12 / 24” x 24”
4 / 24” x 20”
2” Pleated,
30% Eff, MERV 8
30” Bag,
85% Eff, MERV 13
Z
12 / 24” x 24”
4 / 24” x 20”
2” Pleated,
30% Eff, MERV 8
30” Bag,
95% Eff, MERV 14
Y
P
16 / 24” x 24”
2” Pleated,
30% Eff, MERV 8
30” Bag,
85% Eff, MERV 13
Z
16 / 24” x 24”
2” Pleated,
30% Eff, MERV 8
30” Bag,
95% Eff, MERV 14
1
N
12 / 24” x 24”
4 / 24” x 20”
4” Pleated,
30% Eff, MERV 8
30” Bag,
85% Eff, MERV 13
2
12 / 24” x 24”
4 / 24” x 20”
4” Pleated,
30% Eff, MERV 8
30” Bag,
95% Eff, MERV 14
1
P
16 / 24” x 24”
4” Pleated,
30% Eff, MERV 8
30” Bag,
85% Eff, MERV 13
2
16 / 24” x 24”
4” Pleated,
30% Eff, MERV 8
30” Bag,
95% Eff, MERV 14