English, 3 sens - setting the sensor input – Burkert Type 8624 User Manual
Page 25

8624-2 Standard - 23
english
6.6.3
SENS - setting the sensor input
Î Select here whether the sensor is to send 4 - 20 mA or 0 - 10 V to the
controller for the actual value of the controlled variable (factory setting: 0 -
10 V).
Î Next enter the scaling. The range corresponding to the standard signal (4 -
20 mA or 0 - 10 V) is set, i.e. the pressure or flow rate or another type of
controlled variable is entered at 4 mA or 0 V (lower limit) and at 20 mA or 10
V (upper limit).
Settings between 0.000 and 9999 are possible. The unit corresponds to the value
set in the menu item
UNIT.
(factory setting: S LO=0.00; S HI=10.00)
Example:
Lower limit (
S LO) 2,5 bar
4 mA
Upper limit (
S HI) 20 bar
20 mA
=> An actual value signal of 12 mA corresponds in this case to 11.25 bar