31

Operationandfunction

Type 8710, 8711, 8713, 8715

8.2.1. leD default assignment

indicator light status

possible cause

Power indicator (green) on

Power / Autotune

Limit (y)

Error

The device is energized.

Power indicator (green) flashing

Power / Autotune

Limit (y)

Error

The

Autotune function is in

progress.

Communication light (yellow)
on

Power / Autotune

Communication

Error

The device is communicating
via the field bus or the serial
interface.

indicator light status

possible cause

Limit (y) light (blue) on

Power / Autotune

Limit (y)

Error

MFM: indicates that the
measured value has almost
reached the nominal flow-rate.
MFC: indicates that the actuating
variable of the proportional valve
has almost reached 100%. In
practice this usually means that
the pressure on the controller
is not adequate to reach the
required flow-rate.

Limit (y) light (blue) flashing

Power / Autotune

Limit (y)

Error

The device is in an operating
state other than the control mode
or

Autotune function.

Error light (red) on

Power / Autotune

Limit (y)

Error

Minor fault, for example the
Autotune function has failed.

Error light (red) flashing

Power / Autotune

Limit (y)

Error

Major fault, sensor damaged,
internal power supply voltage
incorrect or operating pressure
too high.