Fluid Components International ST100 Series PROFIBUS PA User Manual

Page 12

Advertising
background image

ST100 Series Profibus PA

8

Fluid Components International LLC

Temperature Transducer Block Parameters
The ST100 uses RTDs to measure flow, one of the RTDs measure process temperature. This block provides the measured temperature.

REL. INDEX

PARAMETER

SLOT

INDEX

DATA TYPE (LENGTH)

STORE SIZE READ/WRITE

8

PRIMARY_VALUE

7

24

101(DS-33)

D

5

R

9

PRIMARY_VALUE_UNIT

7

25

UNSIGNED 16

S

2

RW

10

SECONDARY_VALUE_1

7

26

101(DS-33)

D

5

R

11

NOT USED

7

27

12

SENSOR_MEAS_TYPE

7

28

UNSIGNED 8

S

1

RW

13

INPUT_RANGE

7

29

UNSIGNED 8

S

1

RW

14

LIN_TYPE

7

30

UNSIGNED 8

S

1

RW

15 - 18

NOT USED

7

31 - 34

19

BIAS_1

7

35

FLOAT

S

4

RW

20

NOT USED

7

36

21

UPPER_SENSOR_LIMIT

7

37

FLOAT

N

4

R

22

LOWER_SENSOR_ LIMIT

7

38

FLOAT

N

4

R

23

NOT USED

7

39

24

INPUT_FAULT_GEN

7

40

UNSIGNED 8

D

1

R

25

INPUT_FAULT_1

7

41

UNSIGNED8

D

1

R

26 - 32

NOT USED

7

42 - 48

33 - 35

Reserved by PI

7

49 - 51

36

SENSOR_CONNECTION

7

52

UNSIGNED8

S

1

RW

37

COMP_WIRE1

7

53

FLOAT

S

4

RW

The SECONDARY_VALUE_1 parameter is not used, because there is only one temperature

sensor in the ST100.