Table 7. technical data venting (continued) – American Water Heater BCL3 85T390 6NOX User Manual

Page 19

Advertising
background image

19

taBle 7. teChniCal data Venting (Continued)

model (a)BCl3 85t275 6noX
input: 275,000 Btu/hr

total Vent height (feet)

Vent Connector size: 6 inches

6

8

10

15

20

30

50

100

input Btu/hr

rise

Vent Connector diameter (inches)

275,000

1 Ft.

8

8

7

7

6

6

6

6

275,000

2 Ft.

8

8

7

7

6

6

6

6

275,000

3 Ft.

7

7

7

7

6

6

6

6

number of 275 heaters

Combined input in

thousands of Btu/hr

manifold and Common Vent diameters (inches)

2

550,000

10

9

9

8

8

8

7

7

3

825,000

12

12

12

10

9

9

8

8

4

1,100,000

14

14

14

12

12

10

9

9

model (a)BCl3 85t390 6noX
input: 390,000 Btu/hr

total Vent height (feet)

Vent Connector size: 6 inches

6

8

10

15

20

30

50

100

input Btu/hr

rise

Vent Connector diameter (inches)

390,000

1 Ft.

10

9

9

9

8

8

8

8

390,000

2 Ft.

9

9

9

8

8

8

8

8

390,000

3 Ft.

9

9

8

8

8

8

8

8

number of 400 heaters

Combined input in

thousands of Btu/hr

manifold and Common Vent diameters (inches)

2

780,000

12

12

10

10

9

9

8

8

3

1,170,000

14

14

14

12

12

10

10

9

4

1,560,000

16

16

16

14

14

12

12

10

Advertising
This manual is related to the following products: