The following list represents the parameter configuration
required for a Model 705 GWR transmitter intended to
measure overall product level in a SIL 2/3 application.

Please ensure that all Probe-specific parameters are correct
for the GWR probe being used.

PROBE MODEL = As indicated on probe nameplate

PROBE MOUNT = As indicated on probe nameplate

MEASUREMENT TYPE = Level Only

LEVEL UNITS = As indicated on probe nameplate

PROBE LENGTH = As indicated on probe nameplate

LEVEL OFFSET = As required by application

DIELECTRIC = As required by application. (Suggest 1.7–3
for typical hydrocarbon application)

LOOP CONTROL = Level

LOOP CONTROL MODE = Enabled

SET 4mA/SET 20mA = As required by application

DAMPING = As required by application (Default value is 1)

FAULT = As required by application (Default value is
22 mA—do not set to Hold).

BLOCKING DISTANCE = 0 inches

THRESHOLD = Fixed

5.6.3 Write Protection / Locking

Only authorized personnel should be able to change the
transmitter configuration in a device installed in a SIS system.
This requires setting a user password.

The ECLIPSE Model 705 is password protected with a
numerical password between 0 and 255. (Default = 0 means
password is disabled).

The default password must be changed so that password
protection is enabled in a SIS system.

Refer to section 2.6.4 of the Enhanced ECLIPSE Model 705
Installation and Operating Manual 57-600 for additional
information regarding password protection.

Ensure that an exclamation mark (!) appears as the last char-
acter on the first line of the LCD to confirm the present
password has been accepted.

When alterations to the configuration are complete, ensure
the menu has been write-locked with the password to pre-
vent inadvertent changes to the device.

8

57-651 Eclipse

®

SIL Certified Safety Manual for Enhanced Model 705-51AX-XXX