Manual fire and fault tests, Remote fire test – Fire Fighting Enterprises FIRERAY 3000 User Manual
Page 10

10
10. Manual Fire and Fault Tests
After installation or cleaning, it is recommended that a Manual Fire and Fault test is performed:
Fire Test: Slowly half-cover the Receiver. The Controller will indicate Fire after the Fire Delay
Time.
Uncover the Receiver. The Controller will return to Normal state after approximately 5 seconds.
Fault Test: Completely cover the Receiver taking less than 2 seconds to do so. The Controller
will indicate Fault after the Fault Delay time.
Uncover the Receiver. The Controller will return to Normal state after approximately 5 seconds.
11. Remote Fire Test
The Remote Fire Test allows the user to perform a Fire Test from the System Controller.
The Remote Fire Test is acceptable for Fire Authority Acceptance and Routine Maintenance per
UL 268-5.
Receiver Fire LED Test
The Receiver will signal 'Fire',
the System Controller will stay
Normal.
Press
to exit without
performing the test.
Relay / Controller Wiring Test
The System Controller signals
'Fire' to the Fire Control Panel.
Press
or
to exit.