HRV and ERV Typical Installations (cont’d)

9

HORIZONTAL

32” clearance is recommended for cleaning of the core/servicing the unit.

(use appropriate access door size)

• Dampers are installed for horizontal installation. For vertical installation both dampers have
to be turned so they can open properly and close when there is any backdraft.

Make sure no screw will interfere the function of the backdraft damper flaps while

installing the duct work to the HRV/ERV.

STRAPPING SYSTEM:

(optional)

Allows one person installation for
vertical and horizontal installation.

VERTICAL

Map 1-3 are for Aluminum Core (RHRV-D100A). Map 4-6 are for Polypropylene / Plastic Core (RHRV-D100P).

Map 7-9 are for ERV / Enthalpy Core (RERV-D100).

After installation make sure the HRV/ERV is properly leveled. If not levelled correctly, then defrost will not

perform effectively and/or unit may frost in winter.

Also make sure you have proper defrost on wall - controller according to HRV / ERV model no./ core type.

Note:

UP

UP

PULL

DOWN

Strap

jtantay 01.28.1

1

NOT SUPPLIED*

jtantay 12.23.1

1

Vibration
Spring*

Washer*

Screw*

CHAIN MOUNTING
SYSTEM:

(optional)

Available for both
horizontal & vertical
installation.

Chain*

Backdraft
Damper

Concrete

Concrete

Wooden Joist

Bracket

(Supplied)

Grommet*

Washer*

Backdraft Damper

Deluxe Unit
Shown

Screw*

Flap

Flap

Backdraft Damper

27 "

9"

21"

3

4

/