Battery supply, Installation, Nstallation – ADC ACE-COM L1 User Manual

Page 15

Advertising
background image

LTPH-UM-1088-02, Issue 2

Installation

ThinMux Chassis

January 3, 2002

5

Field-Effect Transistor (MOSFET). When set to ON, resistance is 35

at

85°C (worst case). The switched current must be less than 80 mA, and the
switched voltage must be less than 135V. If a coil relay or other inductive
load is used, a protection diode must be connected between the alarm signal
and the COM signal to prevent damage to the solid state relay. ADC does not
provide the diode with the ThinMux chassis. The diode must be purchased
separately. Use Motorola diode part number 1N4004 or equivalent.

B

ATTERY

S

UPPLY

The battery supply terminals are located on the rear of the chassis under the
common access panel (see

Figure 1 on page 2

). Five AWG 16 wires connect

the Return B, -48B, Return A, -48A, and Frame Ground to the power source.
To wire power A and B inputs, attach A and B power leads from the fuse
panel or office battery to the appropriate screw connector on the terminal
block. For more information, refer to

“Connecting Power” on page 10

.

I

NSTALLATION

Before installing the ThinMux Chassis, visually check its
packaging to ensure that it has sustained no shipping
damage. Immediately report any damage to the shipping
agent. See

“Appendix C - Product Support” on page 19

.

Advertising