10 cc-link related parameters – IAI America PCON-CFA User Manual

Page 154

Advertising
background image

4. PCON-CA/CF

A

CC-Link

148

4.10 CC-Link Related Parameters

The parameters related to CC-Link are from No. 84 to No. 86, No. 90 and No. 159.

Classification: C: External Interface Related

No Classification Symbol

Name

Default Value set in the Factory

before Delivery

1
°

83

Refer to instruction manual for

the controller for the parameters

No. 1 through No. 83.

84

C

FMOD Field Bus Operation Mode

0

85

C

NADR Field Bus Node Address

1

86

C

FBRS Filed Bus Communication

Speed

0

87

C

NTYP Network Type

1

90

C

FMIO Filed Bus I/O Format

3

159

C

FBVS FB Half Direct Mode Speed Unit

0

z

Filed Bus Operation Mode (No. 84 “FMOD”)

The operation mode is set using the values 0 to 4 for the parameter No. 84.

Parameter No. 84

Set Value

Mode Name

Station Data and No. of

Occupied Stations

Description

0 (Set in delivery) Remote I/O Mode Remote Device Station:

One Station

The operation is performed using the

PIO (24V I/O) through the CC-Link.

1

Position/Simplified

Direct Value Mode

Remote Device Station:

One Station

The target position can be set directly

using the value or the operation can be

performed using position data value.

The other values required for the

operation are set on the position data.

2

Half Direct Value

Mode

Remote Device Station:

Two Stations

In addition to the target position, the

speed, acceleration/deceleration and

pressing current value are set directly

using the values to perform the

operation.

3

Full Direct Value

Mode

Remote Device Station:

Four Stations

All the values related to the position

control are set using the values to

perform the operation.

4

Remote I/O Mode 2 Remote Device Station:

One Station

The current position and current speed

reading functions are added to the

functions in the remote I/O mode.

z

Field Bus Node Address (No. 85 “NADR”)

The remote station No. is set for the parameter No. 85.

Setting Range: 1 to 64 (When the system is delivered it has been set to “1”).

z

Field Bus Communication Speed (No. 86 “FBRS”)

The communication speed is selected for the parameter No. 86.

Parameter No. 86

Set Value

Communication Speed

0 (Set in delivery)

156kbps

1

625kbps

2

2.5Mbps

3

5Mbps

4

10Mbps

Except for the above

Baud Rate Setting Error