These designs comply with the current edition of the American
National Standard for Gas Water Heaters, Volume III,
ANSI Z21.10.3 / CSA 4.3 as an automatic circulating tank water
heater, and automatic storage water heaters.

Detailed installation diagrams are found in this manual. These
diagrams will serve to provide the installer with a reference for the
materials and methods of piping necessary. It is highly essential
that all water, gas piping and wiring be installed as shown on the
diagrams.

Particular attention should be given to the installation of
thermometers at the locations indicated on the diagrams as these
are necessary for checking the proper functioning of the heater.

In addition to these instructions, the equipment shall be installed in
accordance with those installation regulations in force in the local
area where the installation is to be made. These shall be carefully
followed in all cases. Authorities having jurisdiction should be
consulted before installations are made.

In the absence of local codes, the installation must comply
with the current editions of the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and the National Electrical Code,
NFPA 70 or CAN/CSA-B149.1, the Natural Gas and Propane
Installation Code and CSA C22.1, the Canadian Electrical Code. All
documents are available from the Canadian Standards Association,
8501 East Pleasant Valley Road, Cleveland, OH 44131. NFPA
documents are also available from the National Fire Protection
Association, 1 Batterymarch Park, Quincy, MA 02269.

FOREWORD

ROUGH-IN-DIMENSIONS

GAS VALVE PIPING

BTH-300

1 1/4" NPT

BTH-400

1 1/4" NPT

Recovery capacities are based on heater performance at 96% thermal efficiency.

U.S. Gallons/Hr and Litres/Hr at TEMPERATURE RISE INDICATED

TYPE OF

INPUT

Approx.

20F°

30F°

40F°

50F°

60F°

70F°

80F°

90F°

100F° 110°

120F°

130F°

140F°

MODEL

GAS

BTUH

KW

Capacity

11C°

17C°

22C°

28C°

33C°

39C°

44C°

50C°

56C°

61C°

67C°

72C°

78C°

300,000

130 US Gals.

GPH

1746

1164

873

699

582

499

436

388

349

318

291

269

250

88

492 Litres

LPH

6610

4406

3304

2644

2203

1888

1652

1469

1322

1201

1102

1017

945

300,000

130 US Gals.

GPH

1746

1164

873

699

582

499

436

388

349

318

291

269

250

88

492 Litres

LPH

6610

4406

3304

2644

2203

1888

1652

1469

1322

1201

1102

1017

945

399,900

130 US Gals.

GPH

2328

1552

1164

931

776

665

582

517

466

423

388

359

332

117

492 Litres

LPH

8813

5875

4406

3525

2938

2518

2203

1958

1763

1602

1469

1356

1259

399,900

130 US Gals.

GPH

2328

1552

1164

931

776

665

582

517

466

423

388

359

332

117

492 Litres

LPH

8813

5875

4406

3525

2938

2518

2203

1958

1763

1602

1469

1356

1259

TABLE 1 RECOVERY CAPACITIES.