Standalone units (fr10 to fr12), 11. also see to that the, Ab c – TREND NX Variable Speed Drives User Manual
Page 53
Advertising

36 • vacon
INSTALLATION
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
5
A
B
C
Type Cooling
air
required
[m
3
/h)
0004—0012 NX_2
0003—0012 NX_5
70
0017—0031 NX_2
0016—0031 NX_5
0004—0013 NX_6
190
0048—0061 NX_2
0038—0061 NX_5
0018—0034 NX_6
425
0075—0114 NX_2
0072—0105 NX_5
0041—0052 NX_6
425
0140—0205 NX_2
0140—0205 NX_5
0062—0100 NX_6
650
0261—0300 NX_2
0261—0300 NX_5
0125—0208 NX_6
1300
Table 5-11. Required cooling air
5.2.2
Standalone units (FR10 to FR12)
Mounting space dimensions
[mm]
A
B
C
800
200
20
Table 5-12. Mounting space dimensions
Type
Cooling air required
[m
3
/h)
0385—0520 5
0261—0416 6
2600
0650—0730 5
0460—0590 6
3900
0820—1030 5
0650—0820 6
5200
Table 5-13. Required cooling air
Figure 5-12. Installation space