Operations menu – Watlow EZ-ZONE PM Express Limit User Manual

Page 18

Advertising
background image

EZ-ZONE PM Limit Express

• 18 •

Operations Menu

Operations Menu

Display

Parameter Name Description

Range

Defaults are shown bold

[`LL;S]

[ LL.S]

Limit Low Set Point

Set the low process value that will trig-

ger the limit.

Appears if: Limit sides set to low or both.

-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 0.0°F or -18.0°C

[`Lh;S]

[ Lh.S]

Limit High Set Point

Set the high process value that will trig-

ger the limit.

Appears if: Limit sides set to high or both.

-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 0.0°F or -18.0°C

[`A;Lo]

[ A.Lo]

Alarm Low Set Point
Process - set the process value that will

trigger a low alarm.

Appears if: Alarm Type (A.ty) is set to

Process Alarm

-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 32.0°F or 0.0°C

[`A;hi]

[ A.hi]

Alarm High Set Point

Process - set the process value that will

trigger a high alarm.

Appears if: Alarm Type (A.ty) is set to

Process Alarm

-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 300.0°F or 150.0°C

[`i;CA]

[ i.CA]

Calibration Offset

Set an offset value for a process output.

Appears if: Always

-1,999.000 to 9,999.000°F or units
-1,110.555 to 5,555.000°C

0.0

[````]

PAr1

[````]

PAr2

[`ll;s]

Limit Low Set Point

[`lh;s]

Limit

High Set Point

[`A;lo]

Alarm Low Point

[`A;hi]

Alarm High Point

[`i;Ca]

Calibration Offset

Operations Menu

Upon power up of the control,

using the advance key will scroll

through the various prompts found

in the Operations Menu. At any

point within the Operations menu

to return to the default display push

the Reset

key.