Yokogawa EJA310A User Manual
Eja / ejx fieldguide, Analog output signal standard and namur ne43, Namur ne43 analog output signal
 
EJA / EJX 
FieldGuide 
 
 
Analog Output Signal 
Standard and Namur NE43 
FGP-502
Copyright 2009
1st Edition 01/2009
Yokogawa Corporation of America 
2 Dart Road; Newnan, Georgia U.S.A. 30265 
Yokogawa EJA and EJX series Brain and HART Protocol 
transmitters have an Analog Output Signal (4 to 20 mA) 
corresponding to the Primary Variable. The Analog Output 
Signal is generated from the digital signal supplied by the 
DP
harp
sensor by a 15 Bit D/A signal converter. This conversion
has a resolution of 0.004%. The transmitters are designed to 
drive output signals slightly greater than the 4 to 20mA “Base” 
signal. The intention is to set analog alarm thresholds 
recognizably beyond the normal operating 4 to 20 mA range, 
to indicate measurement out of range, and to set further alarm 
thresholds to indicate a fault condition. 
Measurement Out-of-Range 
Standard Analog Output Signal
Yokogawa EJA and EJX transmitters
 
Standard Analog Output EJA (with option /F1) and EJX 
transmitters are factory set to have an Analog Output – Lower Limit 
(AO-LL) and Analog Output – Upper Limit (AO-UL) of 3.6mA and 
21.6mA respectively [EJA transmitters without Option /F1 output 
limits are 3.2mA to 21.6mA]. This allows for a small amount of 
linear over-range process readings. This linear over-range signal is 
refer to Signal Saturation. During operation, once the AO-LL or 
AO-UL limits are reached, the current signal locks to the respective 
limit and the transmitter communicates a Measurement Out-Of-
Range event to the control unit via the locked analog signal and 
digital communication (Brain or HART); and the indicator (if 
equipped) displays an error code. Once the normal pressure is 
regained, the transmitter clears the error codes, unlocks the analog 
signal and begins to operate as normal. 
 
Example: An EJA110A or EJX110A transmitter is ranged for 
0 to 100 inH
2
O (4 to 20mA).
 
 
 
 
 
 
 
 
The Signal Saturation can be controlled by setting the respective 
AO-LL and AO-UL. The AO-LL and AO-UL are programmable 
within the parameter limits of the transmitter via the digital 
communication protocol. Set the limits by entering the value to the 
parameter noted below. 
 
 
Ensure that the control unit receiving the analog signal is setup to 
recognize the settings used. 
 
Namur NE43 Analog Output Signal
Yokogawa EJA and EJX transmitters
 
NAMUR NE43 is a standard used to define the operating AO-LL 
and AO-UL values of the analog output signal. Similar to the 
Standard analog output signal, Namur NE43 transmitters are 
designed to output signals greater than the 4 to 20mA “Base” 
signal; allowing for a small amount of linear over-range process 
readings (Signal Saturation). Namur NE43 transmitters set the AO-
LL and AO-UL to 3.8mA (-1.25%) and 20.5mA (103.1%) 
respectively. Namur NE43 thresholds are set and can not be 
programmed to different values through the Digital protocol. 
 
Ensure that the control unit receiving the analog signal is setup to 
recognize the Namur NE43 settings used.