Oil drain & air purge – MAHLE RTI AC800 User Manual

Page 10

Advertising
background image

RTI Technologies, Inc.

October 6, 1999

Page 9

0

F

R12

R134a

30

42

40

32

44

42

34

46

44

36

48

46

38

50

49

40

52

51

42

54

54

44

57

56

46

59

59

48

61

61

50

64

64

52

66

67

54

69

70

56

72

72

58

74

76

60

77

78

62

80

82

64

83

85

66

85

88

68

88

92

70

92

95

72

95

97

74

98

104

76

102

107

78

105

110

80

108

114

82

112

118

84

115

123

86

118

127

88

123

130

90

127

135

92

130

140

94

135

145

96

138

148

98

143

153

100

147

157

102

150

163

104

155

167

106

160

173

108

165

180

110

168

185

112

173

190

114

178

195

116

183

200

118

188

207

120

193

213

Purge Chart

OIL DRAIN & AIR PURGE

Oil and Non-condensable Gas (Air) are separated from
the recovered refrigerant and MUST be removed
following EACH recycling procedure as follows:

Note: AC800 must be connected to power source.

1.

Press and hold the Purge Button (below the Purge
Gauge) for 5 seconds, and then release it.

2.

SLOWLY open the Oil Drain Valve (behind push
up door in front of AC800) to drain any oil which
may have been removed from the A/C System. A
cup is provided to collect the oil.

Unless the A/C System had previously been
overfilled, the AC800 will typically not remove
more than a tablespoon of oil, making replenishment
unnecessary.

LEAVE THE OIL DRAIN VALVE OPEN...

3.

Read temperature on Thermometer in center of
AC800 control panel.

4.

Locate the pressure (PSIG) corresponding to this
room temperature (

0

F) in the chart on the top of the

AC800. This chart is reproduced at the right.

If the pressure indicated on the Purge Gauge is
greater than that determined from the chart:

Press and hold the Purge Button until the Purge
Gauge pressure goes down to the pressure
determined from the chart. Any Non-condensable
Gas will be vented through the Oil Drain Valve at
this time.

5.

Close the Oil Drain Valve.

6.

Press and hold the Purge Button for 5 seconds. This
permits any residual Non-condensable Gas to be
recirculated for reprocessing during the next recycle
procedure.