Oil drain & air purge – MAHLE RTI AC800 User Manual
Page 10
RTI Technologies, Inc.
October 6, 1999
Page 9
0
F
R12
R134a
30
42
40
32
44
42
34
46
44
36
48
46
38
50
49
40
52
51
42
54
54
44
57
56
46
59
59
48
61
61
50
64
64
52
66
67
54
69
70
56
72
72
58
74
76
60
77
78
62
80
82
64
83
85
66
85
88
68
88
92
70
92
95
72
95
97
74
98
104
76
102
107
78
105
110
80
108
114
82
112
118
84
115
123
86
118
127
88
123
130
90
127
135
92
130
140
94
135
145
96
138
148
98
143
153
100
147
157
102
150
163
104
155
167
106
160
173
108
165
180
110
168
185
112
173
190
114
178
195
116
183
200
118
188
207
120
193
213
Purge Chart
OIL DRAIN & AIR PURGE
Oil and Non-condensable Gas (Air) are separated from
the recovered refrigerant and MUST be removed
following EACH recycling procedure as follows:
Note: AC800 must be connected to power source.
1.
Press and hold the Purge Button (below the Purge
Gauge) for 5 seconds, and then release it.
2.
SLOWLY open the Oil Drain Valve (behind push
up door in front of AC800) to drain any oil which
may have been removed from the A/C System. A
cup is provided to collect the oil.
Unless the A/C System had previously been
overfilled, the AC800 will typically not remove
more than a tablespoon of oil, making replenishment
unnecessary.
LEAVE THE OIL DRAIN VALVE OPEN...
3.
Read temperature on Thermometer in center of
AC800 control panel.
4.
Locate the pressure (PSIG) corresponding to this
room temperature (
0
F) in the chart on the top of the
AC800. This chart is reproduced at the right.
If the pressure indicated on the Purge Gauge is
greater than that determined from the chart:
Press and hold the Purge Button until the Purge
Gauge pressure goes down to the pressure
determined from the chart. Any Non-condensable
Gas will be vented through the Oil Drain Valve at
this time.
5.
Close the Oil Drain Valve.
6.
Press and hold the Purge Button for 5 seconds. This
permits any residual Non-condensable Gas to be
recirculated for reprocessing during the next recycle
procedure.