Examples of i/o’s – Mammoth 1/2 to 6 Tons: High Efficiency Single Circuit Horizontal and Vertical (A-Vintage) User Manual
Page 17
17
MAMM-WSHP-IOM-1MA
Examples of I/O’s
INPUTS
Point
Description
UD #1
+Pulse
BMS Supply Air, Duct Static Reset or Room Air Temperature Setpoint
UD #2
Room Air Temperature
UD #3
RTD/Therm/Dry
System Switch
Emergency Shut Down
Remote Start
UD #4
Contact, 0-10VDC,
High Static
Low Static
VFD in Bypass
UD #5
0-20MA
Economizer Lockout
Cooling Lockout
Heating Lockout
UD #6
Supply Fan Status
Compressor Fault
Condensate Overflow
UD #7
Duct Static Pressure or Airflow Switch
UD #8
Filter Static Pressure or Dirty Filter Switch #1
UD #9
Outside Air Temperature (AiSE Only)
UD #10
Condenser Water Temperature
UD #11
Entering Air Temperature or Return Air Temperature (AiSE)
UD #12
Supply Air Temperature
OUTPUTS
Point
Description
UO #1
4-20mA, 0-10Vdc
Spare
UO #2
Heating Source Control Signal
UO #3
0-10 Vdc
Economizer Valve (WiSE)/Damper Control Signal (AiSE)
UO #4
WiSE Bypass Valve Signal
UO #5
Spare
UO#6
Supply Fan VFD Control Signal
DO #1
120 VAC
Start Supply Fan
DO #2
FORM C
Start Condenser Pump or Switch Reversing Valve
DO #3
Field-Lin (MWU or Open Min OA)
DO #4
Common Alarm
DO #5
Compressor Call #2
DO #6
Compressor Call #1