Performance Troubleshooting
Performance
Troubleshooting
Heating Cooling Possible
Cause
Solution
Unit doesn’t operate in cooling
X
X
Low refrigerant charge
Check superheat and subcooling
X
X
Restricted metering de-
vice
Check superheat and subcooling– replace
X
Defective reversing valve
Perform RV touch test
X
X
Unit
undersized
Recheck loads & sizing. Check sensible, cooling load and heat pump ca-
pacity
X
X
Scaling in waterside heat
exchanger
Perform scaling check and clean if necessary
X
X
Inlet water too hot or cold
Check load, loop sizing, loop backfill, ground moisture
High head pressure
X
Reduced or no water flow
in cooling
Check pump operation or valve operation/setting. Check water flow; adjust
to proper flow rate
X
Inlet water to hot
Check load, loop sizing, loop backfill, ground moisture
X
Scaling in waterside heat
exchanger
Perform scaling check and clean if necessary
X
X
Unit
overcharged
Check superheat and subcooling
X
X
Non-condensable in
system
Vacuum system, reweigh in charge
Low suction pressure
X
Reduced water flow in
heating
Check pump operation or valve operation/setting. Check water flow adjust
to proper flow rate
X
Water temperature out of
range
Bring water temp within design parameters
X
X
Insufficient charge
Check for refrigerant leaks