S caution – Hired-Hand Polar Cool: Wall Mount Kit User Manual
Page 2
RollSeal, Inc. • 1751 County Road 68 • Bremen, Alabama 35033 • Phone 256-287-7000 • Fax 256-287-7010
Sheet Part No. 4801-5208 rev 1-07
Page 2 of 4
Bracket/Wall connections must be sufficient to
resist a working load of 750 pounds (340 KG) vertical
shear on both girts and 900 pounds (408 KG) pull-out
on the upper girt. See Figure 5. RollSeal assumes no
responsibility for inappropriate connections.
Position the PolarCool atop the Wall Mount Bracket.
Slide the Front Adjustable Bracket against the front of the
PolarCool cabinet. Secure with 3/8” cap screws, washers, and
nuts as shown in Detail A above. Appropriate sealing tape or
weather seal should be placed around the PolarCool cabinet.
6
S Note !
No flashing, weather seal, or tape is supplied with PolarCool Wall Mount Kit.
!
Figure 5- Sheer Strength
Requirements
Position the top edge of the Hat sections flush
with the bottom of the wall opening. Center wall mount
assembly in opening. Level the Wall Mount Assembly
and attach firmly to wall. See Figure 4. Wall fasteners
are not provided in the Wall Mount Kit.
4
5
Figure 4 – Flush Wall Mount
Lock Nut
3/8”-16
(1001-1457)
Cap Screw
3/8”-16 x ¾”
(1001-1422)
Figure 3 – Bracket Assembly
900 lbs.
750 lbs.
750 lbs.
Wall
Girts
S Caution !
Due to the weight of the PolarCool cabinet, proper
lifting apparatus must be employed!
!
Cap Screw
3/8”-16 x ¾”
(1004-1422)
Detail A
Lock Nut
3/8”-16
(1001-1457)
Flat Washer
3/8”
(1003-1462)
NOTE: Front Adjustable Bracket is not
installed until after the PolarCool is
mounted.