Overview – Aquametrix 2300 Multi-Input Controller User Manual User Manual
Page 5

N116-133 AquaMetrix 2300 Installation and Operation Manual
Page 5
1. Overview
1.1. Introduction
The AquaMetrix 2300 Controller is a multi-input controller that is web-enabled such that it can
be setup in minutes from any web browser. It contains a number of Set-up Wizards to aid the
user in entering information, much of which is not reproduced in this manual. The Wizards
and most other screens in the 2300 Controller are organized by a dialogue followed by a
summary page with “Submit” and “Cancel” at the bottom. The user may familiarize
himself/herself with the 2300 by going through most menu functions and just hitting “Cancel”
and not “Submit”.
The standard configuration inputs up four 4-20mA analog sensors and three digital/frequency
inputs for flow monitoring. Outputs include four relays and unlimited email/text notifications.
The 2300 Controller provides remote viewing capability and configuring with password from
any connected web browser. It also provides data logging with downloading or emailing of
log files in CSV format. There is also one available slot for an optional card, which can expand
digital inputs or relays outputs, or add analog outputs.
1.2. Specifications
Table 1 - Specifications
Inputs
Analog
Four 4-20 mA powered or unpowered current loops
Pule Rate
Two optically isolated inputs suitable for flow sensors, up to 24 VDC or 120 VAC
Counter
One accumulator for tracking equipment on time
Contacts
Four contact sensing inputs for alarm acknowledgement or remote resets.
Outputs
Relays
Four 120V/240 V @ 10A/5A expandable to eight*
Alerts
Emails and/or texts for alarms, relay actions, errors, or reminders
Web
Remote viewing with a browser on a computer, tablet, or smart phone. Remote
programming from any of these.
Data logging
Logging of CSV files directly to micro SD card
Digital Outputs
Modbus TCP over Ethernet connection
Analog Outputs
Optional: Four non-isolated 4-20 mA outputs proportional to any reading.*
Control
Web or LAN
Viewing with a browser on a computer, tablet, or smart phone. Setup and
control from any of these. Multi-user password protected.
Front Panel
Status, Probe enable/disable/calibrate, System Configuration
Ratings