Figure #4 – Detcon IR-542 User Manual

Page 11

Advertising
background image

3.6 S

TART

U

P

Upon completion of all mechanical mounting and termination of all f ield wiring, apply system power and observe

the following normal conditions:

a)

The “Fault” LED is off.

b)

A reading of 0.00% CO2 should be indicated upon conclusion of a 12 second “warming up” cycle.

Note 1: If the display contrast needs adjustment, refer to section 3.10.

3.6.1 Initial Operational Tests

After a warm up period has been allowed for, the sensor should be checked to verify sensitivity to carbon dioxide

gas.

Material Requirements

*

Detcon PN 6132 Threaded Calibration Adapter

*

Span Gas 50% of full-scale range CO2 in air at a controlled f low rate of 200 ml/min.

a)

Attach the calibration adapter to the threaded sensor housing. Apply the test gas at a controlled f low rate of

200 ml/m. Observe that the LCD display increases to a level of 20% of full-scale range or higher.

b)

Remove the test gas and observe that the LCD display decreases to

“0.00 % CO2”.

Initial operational tests are complete. Detcon CO2 sensors are pre-calibrated prior to shipment and will, in most

cases, not require signif icant adjustment on start up. However, it is recommended that a complete calibration test

and adjustment be performed within 24 hours of installation. Refer to calibration instructions in later text.

Detcon Model IR-540/IR-542 Carbon Dioxide Sensor PG.11

1 2 3 4

R

E

D

B

R

N

W

H

T

B

LK

Remote Transmitter

IR-540-RT

Remote Sensor

IR-540-RS

WHT

BLK
YEL

BLU

RED
BRN

5 6

Y

E

L

B

LU

Figure #4