Fire-Lite 411UDAC Fire Alarm Communicator User Manual
Page 58

58
411UDAC Manual — P/N 51073:E 9/20/2013
Central Station Communications
Ademco Contact ID Format Event Code Description
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
Time
Date
Rcvr/Line ID
SSSS
QXYZ
GG CCCC
11:28
03/25
11
7777
E110
00 C001 - general fire alarm on Channel/Input 1
11:28
03/25
11
7777
E111
00 C002 - smoke detector alarm on Channel/Input 2
11:28
03/25
11
7777
E380
00 C003 - fault on Channel/Input 3
11:28
03/25
11
7777
R110
00 C001 - Channel/Input 1 alarm restored
11:28
03/25
11
7777
R111
00 C002 - smoke detector Channel/Input 2 restored
11:28
03/25
11
7777
R380
00 C003 - Channel/Input 3 fault restored
11:28
03/25
11
7777
E158
00 C004 - high temperature, Channel/Input 4
11:28
03/25
11
7777
E151
00 C004 - gas detected, Channel/Input 4