3.6.10 Interface cable
The data interface cable is a shielded, 3 x 1.5 mm
2
LIYCY cable. The standard length 10 m /
32.8 ft is included in the delivery.
1 Strip the conductor to dimension a.
2 Trim the outer shield to dimension b and pull it over the outer sheath.
3 Crimp the wire end ferrules onto the conductors 1, 2 and 3.
Connect the shielding at both sides of the cable via the special cable gland.
Preparing the interface cable
Figure 3-33: Preparing the interface cable
a = 100 mm / 4"
b = 10 mm / 0.4"
Connecting shielding via special cable gland
Figure 3-34: Connecting the shield within the cable gland
1 Wires
2 Isolation
3 Shielding
4 Isolation
5 Feed cable through dome nut and clamping insert and fold shielding over clamping insert. Make sure that the braided
shield overlaps the O-ring by 2 mm / 3/32".
6 Push clamping insert into body.
7 Tighten the dome nut.