Profibus pa – KROHNE FC 300 Converter PROFIBUS PA-DP User Manual

Page 24

Advertising
background image

3

PROFIBUS PA

24

IFC 300

www.krohne.com

02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en

For both replacements 1. and 2., there are 2 options how to deal with the GSDs. In order to
provide communication between "IFC300 with PROFIBUS MBP interface" and the PLC, you may -
in principle – use the GSD of the "IFC090PA" ("KROHF401.GSD" or "YP01F401.GSD") and

alternatively - the GSD of the "IFC300 with PROFIBUS MBP interface" ("KR024501.GSD" or

"YP024501.GSD").

However, both sets of GSDs, when applied, do not

do not

do not

do not provide the same level of functionality in the

PLC. The available PROFIBUS functionality of the "IFC300 with PROFIBUS MBP interface" in the
PLC as function of installed flow sensor and GSD used for integration into the PLC is as follows:

If the GSDs of the "IFC090PA" ("KROHF401.GSD" or "YP01F401.GSD") are used…

• The IFC090PA parameter set for the PLC control software will be maintained, i.e. there is no

adaptation needed with reference to the replaced interface of the IFC300 with PROFIBUS
MBP interface.

• In this usage of the GSD the PA Profile 2.0

PA Profile 2.0

PA Profile 2.0

PA Profile 2.0 functionality is provided in the PLC for both

replacements, i.e. it is not possible to reset the PA totalizer via the PLC.

If the GSD of "IFC300 with PROFIBUS MBP interface” (KR024501.GSD or
YP024501.GSD) is used…

• The IFC090PA parameter set for the PLC control software has to be adapted with reference to

the IFC300 PROFIBUS MPB interface.

• In this usage of the GSD the PA Profile 3.0

PA Profile 3.0

PA Profile 3.0

PA Profile 3.0 functionality is provided and all diagnostic features

of the "IFC300 with PROFIBUS MBP interface" are being made available.

Installed flow sensor

Integration into the PLC via

IFC090PA.GSD
KROHF401.GSD

IFC300 with PROFIBUS MBP
interface GSD
KR024501.GSD

IFS…FLUX flow sensor

(Option 1.)

"IFC090PA" profile 2 functionality "IFC300 with PROFIBUS MBP

interface" functionality (some

"IFC300 with PROFIBUS MBP

interface" self-test functions not

available)

OPTIFLUX flow sensor (Option 2.)

"IFC090PA" profile 2 functionality "IFC300 with PROFIBUS MBP

interface" functionality

How to deal with the PA

parameter set in the PLC Ctrl

software

The "IFC090PA" parameter set

for the PLC Ctrl software can be

used as existing in the PLC

The "IFC090PA" parameter set

for the Ctrl software has to be

adapted with reference to the

interface of "IFC300 with

PROFIBUS MBP interface"

Advertising