ELECTRICAL CONNECTIONS

3

5

MFC 300

www.krohne.com

02/2013 - 4001086702 - AD MFC 300 FF R02 en

3.1 Installation in hazardous area and bus cable

We recommend that a Foundation Fieldbus network in the hazardous area should be projected in
accordance with PTB's FISCO model. The FISCO model is based on the following conditions:

• All electrical components which should be connected to the bus must be approved according

to the FISCO model (even the termination).

• The maximum cable length should not exceed 1000 m / 3280.8 ft.
• The approved input values of the field devices (U

0

, I

0

, P

0

) comply to the output values of the

power supply (e.g. segment coupler) according to: U

0

≤ U

i

; I

0

≤ I

i

; P

0

≤ P

i

.

• The values of the cable must be within the following ranges:

R' = 15…150 Ω/km; L' = 0.4…1 mH/km; C' = 45…200 nF/km
equivalent to
R' = 24…240 Ω/mile; L' = 0.65…1.6 mH/mile; C' = 72…320 nF/mile

Other limitations for the cable than the FISCO limitations are not existent. Nevertheless, a
twisted pair and shielded cable is strongly recommended.

Example: a good quality cable could have the following data: 44 Ω/km = 70.4 Ω/mile; <90 nF/km
= <144 nF/mile; attenuation at 39 kHz: <3 dB/km = <4.9 dB/mile; impedance 100 Ω at 31.25 kHz.

3.2 Foundation Fieldbus electrical connection

The output and input groups are electrically isolated from each other and from all other input
and output circuits.

3.3 Cable types

The cable types are specified according to IEC 61158-2. Shielded cables offer the advantage of
malfunction-free operation with adequate protection against electromagnetic influences, and
make it possible to employ the full performance of the Foundation Fieldbus system.

In non-hazardous areas the maximum number of field devices is limited to 32. For detailed
information refer to the following table.

In non-hazardous areas the ignition protection class of the devices and the limited electric power
available limit the number of field devices to 4.

DANGER!
The signal converter must be properly grounded to avoid personnel shock hazard. All directions,
operating data and connection diagrams do not apply to devices used in hazardous areas; in such
cases, read the special Ex instructions without fail!

Core cross-section

0.8 mm

2

or

AWG 18

0.32 mm

2

or

AWG 22

0.13 mm

2

or

AWG 26

1.25 mm

2

or

AWG 16

Cable type

A

A

A

A

B

B

B

B

C

C

C

C

D

D

D

D

twisted pair,

individually

shielded

individual or

multiple twisted

pairs with overall

shield

multiple twisted

pairs, without

shielding

multiple non-

twisted cables,

without shielding

Max. length

incl. branch line

1900 m / 6200 ft

1200 m / 3900 ft

400 m / 1300 ft

200 m / 650 ft